background image

 
                           120315-40 

   ESPR.BODYA  5056.201-A

 

 

 

 

Important Note for the Commonwealth of Massachusetts: 

 

From Massachusetts Rules and Regulations 248 CMR 5.08: 
 
(a)  For all side wall horizontally vented gas fuelled equipment installed in every dwelling, building or structure used in whole or in part for 
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven 
(7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied. 
 
1. 

INSTALLATION OF CARBON MONOXIDE DETECTORS.  At the time of installation of the side wall horizontal vented gas fuelled equipment, 

the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the 
floor level where the gas equipment is to be installed, in addition, the installing plumber or gas fitter shall observe that a battery operated or hard-
wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall 
horizontal vented gas fuelled equipment.  It shall be the responsibility of the property owner to secure the services of qualified licensed professionals 
for the installation of hard-wired carbon monoxide detectors.   
 
a. 

In the event that the side wall horizontally vented gas fuelled equipment is installed in a crawl space or an attic, the hard-wired carbon 

monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. 
 
b. 

In the event that the requirements of this subdivision cannot be met at the time of completion of installation, the owner shall have a period of 

thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed. 
 
2. 

APPROVED CARBON MONOXIDE DETECTORS.  Each carbon monoxide detector as required in accordance with the above provisions shall 

comply with NFPA 720 and be ANSI/UL 2034 listed as IAS certified. 
 
3. 

SIGNAGE.  A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) 

feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fuelled heating appliance or equipment.  The sign shall 
read, in print size no less than one-half (1/2) inch in size, ‘‘GAS VENT DIRECTLY BELOW.  KEEP CLEAR OF ALL OBSTRUCTIONS’’. 
 
4. 

INSPECTION.  The state or local gas inspector of the side wall horizontally vented gas fuelled equipment shall not approve the installation 

unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 
5.089(2)(a) 1 through 4. 
 
(b)  EXEMPTIONS.  The following equipment is exempt from 248 CMR 5.089(2)(a) 1 through 4. 
1. 

The equipment listed in Chapter 10 entitled ‘‘Equipment Not Required To Be Vented’’ in the most current edition of NFPA 54 as adopted by the 

Board; and  
2. 

Product Approved side wall horizontal vented gas fuelled equipment installed in a room or structure separate from the dwelling, building or 

structure used in whole or in part for residential purposes. 
 
(c) 

MANUFACTURER REQUIREMENTS --- GAS EQUIPMENT VENTING SYSTEM PROVIDED.  When the manufacturer of Product Approved 

side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions 
provided by the manufacturer for installation of the equipment and the venting system shall include:  
1. 

Detailed instructions for the installation of the venting system design or the venting system components; and 

2. 

A complete parts list for the venting system design or venting system. 

 
(d)  MANUFACTURER REQUIREMENTS --- GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.  When the manufacturer of a Product 
Approved side wall horizontally vented gas fuelled equipment does not provide the parts for venting the fuel gases, but identifies ‘‘special venting 
systems’’, the following requirements shall be satisfied by the manufacturer. 
1. 

The referenced ‘‘special venting system’’ instructions shall be included with the appliance or equipment installation instructions; and 

2. 

The ‘‘special venting systems’’ shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions. 
 
(e)) 

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fuelled equipment, all venting instructions, 

all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the 
installation.

 

Summary of Contents for ESPR.BODYA

Page 1: ...iately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed...

Page 2: ...t above grade directly in line with the exhaust vent terminal for the horizontally vented gas fuelled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in...

Page 3: ...ting the Fireplace 19 Surround Installation 20 Venting 21 Vent Terminal Minimum Clearances 22 Venting Components 23 Plumbing and Electrical 24 Gas Supply 25 Gas Pressure Check 25 Gas Pressure Testing...

Page 4: ...3 5 kPa This appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures...

Page 5: ...ng glass is provided with the appliance and shall be installed If the barrier becomes damaged the barrier shall be replaced with the manufacturer s barrier for this appliance Any safety screen guard o...

Page 6: ...refully read this manual and pay close attention to all Safety Warnings The manual contains important information on the unit s safe operation and maintenance When lit for the first time the fireplace...

Page 7: ...the IFC to the gas valve and stepper motor Transmitter Remote Control with LCD Display The Proflame2 Remote Transmitter uses a streamline design with a simple button layout and informative LCD displa...

Page 8: ...ion fan OPERATING PROCEDURE Initializing the System for the first time 1 Install 4 AA batteries into the Esprit battery bay Fig 4 located behind the front surround and underneath the firebox Install t...

Page 9: ...system ON press the ON OFF Key on the Remote transmitter The Remote transmitter LCD display will only show the room temperature Fig 6 or 7 At the same time the Receiver module will turn off the firep...

Page 10: ...his function press the thermostat key Fig 1 The LCD display on the remote transmitter will change to show that the room thermostat is ON and the set temperature is now displayed Fig 10 To adjust the s...

Page 11: ...rol icon Fig 13 Use the Up Down Arrow Keys Fig 1 to turn on off or adjust the fan speed Fig 13 A single beep will confirm reception of the command Figure 14 CPI IPI Selection Figure 13 Fan Control Con...

Page 12: ...mote system or activating manual bypass of the remote system Receiver The life span of the IFC batteries depends on various factors quality of the batteries used the number of ignitions of the applian...

Page 13: ...it to break If the glass becomes cracked or broken it must be replaced before using the fireplace Replacement door can be obtained from your nearest Pacific Energy dealer Do not substitute with any ot...

Page 14: ...lace if necessary It is important that the glass seal be maintained in good condition c Check and replace batteries as needed Note The appliance area must be kept clear and free from combustible mater...

Page 15: ...5056 201 A ESPR BODYA 15 120315 40 OWNER S INFORMATION Lighting Instructions...

Page 16: ...e ANSI Z223 1 NFPA 54 or the National Gas and Propane Installation Code CSA B149 1 A manufactured home USA only or mobile home OEM installation must conform with the Manufactured Home Construction and...

Page 17: ...5056 201 A ESPR BODYA 17 120315 40 INSTALLER INFORMATION Fig 19 Framing At The Corner Fig 20 Minimum Clearance Corner Framing...

Page 18: ...ustible Materials ENCLOSED SIDE WALL 1 75 ENCLOSED BACK WALL NCR ENCLOSED CEILING 4 ECLOSED FRONT WALL 24 From top of the glass EXPOSED SIDE WALL 8 From side of the glass VENT ENCLOSURE 1 EXTERIOR SOF...

Page 19: ...here gas supply piping may be plumbed Various installations are possible such as into an existing wall a corner a built in wall or a wall projection Due to high temperatures do not locate this firepla...

Page 20: ...along the inner edge of the base 2 Install screen with the frame in slots on inner side of the surround base 3 Install the surround front by positioning it so as to clear the notches and secure by ap...

Page 21: ...t adjustment from this chart Note The vent must not exceed a total length of 35 feet Any combination of rise and run may be used but must be constrained to the boundaries of this chart A Maximum of th...

Page 22: ...201 A INSTALLER INFORMATION Fireplace Dimensions This fireplace is certified for use with 4 x 6 5 8 coaxial venting components only It is permitted to only use certified venting for this appliance Ven...

Page 23: ...E Mixing venting components from different manufacturers is inadvisable Venting Components Figure 1 4 x6 5 8 Rigid Piping Cross Reference Chart Figure 29 4 x6 5 8 Rigid Piping Cross Reference Chart Fi...

Page 24: ...licensed electrician must be used to make this connection Gas connection To make the required electrical and gas connections start by positioning the gas fireplace Connect the gas supply line to the...

Page 25: ...s shown in the chart below A drip leg must be installed in the gas supply line going to the gas control valve to minimize the possibility of any loose scale or dirt within the gas supply line from ent...

Page 26: ...test ports on the valve which can be seen in Figure 33 After locating test ports loosen the screws within the ports using a flat tip screwdriver 3 Attach pressure gauge to the test ports 4 Turn gas s...

Page 27: ...ealant needs to be applied to the threads of the new orifice to ensure a proper seal when installed To replace the pilot orifice you will need to remove the pilot hood which is held in place by a spri...

Page 28: ...ot on the bottom of the firebox Fan Installation Removal Figure 38 Fan Installation Removal Fan removal after fireplace installation 1 Remove door surround and glass frame with the glass as seen in Fi...

Page 29: ...n Removal 1 Insert back panel so that it is sitting on ledge at the back of the firebox as shown in Figure 40 2 Insert first side panel by inserting the front edge of the panel into the lip at the fro...

Page 30: ...3 Removal Remove the screws seen in Figure 43 using a screwdriver Turn off main gas supply to unit and disconnect 3 8 flex tubing from inner firebox Also disconnect power cord from inner firebox and r...

Page 31: ...Place the Logs 1 and 2 as seen in Fig 47 than place Log 3 over dowel pin on Log 2 as seen in Fig 48 Place Log 6 to the left side seen in Fig 49 Place side Log 5 and 4 as seen in Fig 50 Place Log 7 as...

Page 32: ...ll the glass evenly spread a thin layer of crushed glass across the entire burner pan as seen in Figure 53 To install the optional rock set simply place desired number of rocks into the fireplace pan...

Page 33: ...d the air baffle at the top of the inner firebox Sometimes on installations that involve vertical venting configurations over 23 feet in height the intake air tends to accelerate down the vent causing...

Page 34: ...ASS 5LB DESERT GASC 5GLDE GLASS 5LB PACIFIC GASC 5GLPA PANEL SETS PORCELAIN PANEL SET BLACK ESPR PNPBKA PORCELAIN PANEL SET TITANIUM ESPR PNPTIA PORCELAIN PANEL SET COFFEE BEAN ESPR PNPCBA PORCELAIN P...

Page 35: ...5 120315 40 INSTALLER INFORMATION Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicin...

Page 36: ...120315 40 36 ESPR BODYA 5056 201 A INSTALLER INFORMATION Fireplace Dimensions Esprit Rating Label...

Page 37: ..._________ ________________________________________________________________________________ ________________________________________________________________________________ ____________________________...

Page 38: ...____________ ________________________________________________________________________________ ________________________________________________________________________________ _________________________...

Page 39: ...5056 201 A ESPR BODYA 39 120315 40 INSTALLER INFORMATION...

Page 40: ...LTD Reproduction adaptation or translation without prior written permission is prohibited except as allowed under the copyright laws For technical support please contact your retailer Web site www pa...

Reviews: