background image

7

SPNE 190913-24

Installation

Your Insert is designed to be installed into a masonry or 
factory-built, zero-clearance fi replace.  The masonry fi replace 
must be built according to the requirements of the Standard 
of Chimneys, Fireplaces, Vents and Solid Fuel Burning ap-
pliances, N.F.P.A. 211 (Latest Edition) or applicable National, 
Provincial, State or local codes.  The installation shall conform 
to CAN/CSA-B365, Installation Code for Solid-Fuel-Burning 
Appliances and Equipment.  The factory-built, zero-clearance 
fi replace and its chimney must be listed per UL 127 or ULC 
S610 standards.
Warning:  Under no circumstances is this heater to be installed 
in a makeshift or "temporary" manner.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE 

SERVICING ANOTHER APPLIANCE.

Fireplace Specifi cations

Your fi replace is required to have the following minimum sizes:
WIDTH (at front) 

 

23 3/4"  (602.44 mm)

WIDTH (at rear)  

 

21-3/4"  (552.5 mm)

HEIGHT   21" 

(533.4 

mm)

DEPTH 

   18" 

(457.2 

mm)

Chimney height 15' (minimum)

A metal tag is provided and is to be fastened to the back 

wall of the fi replace, if the fi replace has been modifi ed to 

accommodate the insert.

Into a Masonry Fireplace

Inspect your fi replace for cracks, loose mortar or other physi-
cal defects.  If repairs are required, they should be completed 
before installing your insert.  
The fi replace chimney must be suitable for wood burning use.  
Check for creosote build up or other obstructions, especially 
if it has not been in use for some time.
The existing fi replace damper is to be locked open or removed 
completely.

WARNING:  Do not remove bricks or mortar from your 

existing fi replace.

Exception:  Masonry or steel, including the damper plate, may 
be removed from the smoke shelf and adjacent damper frame 
if necessary to accommodate a chimney liner, provided that 
their removal will not weaken the structure of the fi replace and 
chimney, and will not reduce protection for combustible materi-
als to less than that required by the National Building Code.
The Insert must be installed in accordance with local and or 
national building codes.  The two methods of fl ue connection 
that are acceptable in most areas are:

Full Flue Liner: (Fig.2) where a stainless steel rigid or fl exible 
liner extends from the Insert fl ue collar to the top of the chimney.
Positive Flue Connection:  where a throat blocker plate and a 
short connector pipe is used.
Note: 

A clean-out door may be required under local codes, 

when a positive fl ue connection is used.  Consult local codes.

Pacifi c Energy highly recommends the use of a full liner 

as the safest installation and providing  optimum perfor-

mance.  When connected to a full liner, the Insert is able to 

draft correctly and will prevent problems such as difficult 

start-ups and smoking out the door. 

For difficult installations, this insert is approved for use 

with a SPND.3OFFSETA - 3” fl ue offset box. Only this 

offset box is approved for use with this insert. The use 

of any other offset box may cause a hazard and/ or void 

any warranty.

Rain Cap

Stainless Steel

Rigid or Flex Liner

Fig. # 2

Full Flue Liner

(Required in Canada)

Mantel or

Top Facing

Summary of Contents for DESIGN-E

Page 1: ...nsult local building inspector or officials about restrictions and installation inspection requirements in your area Super Insert IMPORTANT THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER SAVE THE...

Page 2: ...ustion Air 12 Operation 13 Wood Selection 13 How to Test Your Wood 13 Lighting the Fire 13 Normal Operation 13 Restarting After Extended or Overnight Burns 13 Over Firing 13 More Wood More Heat 14 Pro...

Page 3: ...als about restric tions and installation inspection requirements in your area Clearances Masonry or Factory Built Fireplace Theminimumrequiredclearancestosurroundingcombustible materialswheninstalledi...

Page 4: ...ket Baffle Top heat shield and mounting bolt Baffle Gasket Brick Rails Manifold Some warping of the baffle is normal up to 1 4 or 65cm Replace if the baffle has permanent warping greater than this or...

Page 5: ...t embers by non combustible material extending 16 USA and 18 CANADA to the firing side and 8 to other sides of the unit Consult CAN CSA B365 Installation Code for Solid Fuel Burning appliances and equ...

Page 6: ...6 SPNE 190913 24 43 3 8 6 1 2 29 3 16 23 3 4 21 1 2 21 1 8 36 8 3 4 20 3 4 18 28 1 8 9 1 2 10 21 Dimensions...

Page 7: ...een in use for some time The existing fireplace damper is to be locked open or removed completely WARNING Do not remove bricks or mortar from your existing fireplace Exception Masonry or steel includi...

Page 8: ...pe Note A clean out door may be required under local codes when a direct flue connection is used Consult local codes 3 Push the Insert into position inside the fireplace and at tach the connector pipe...

Page 9: ...and thermal snap switch Take note of where the wires are routed and secured They must be positioned correctly to avoid damage 3 Loosen the two bolts that secure the ash lip to the firebox carefully l...

Page 10: ...ch Fig 16 refit ash lip sides and top Ensure that the power cable is correctly routed through the surround and it is not touching the firebox side Wire placement is important to prevent damage to wire...

Page 11: ...on page 9 and then remove the decorative top by loosening the two wing bolts underneath and sliding it out of the brackets Fig 18 4 Slide the assembled surround from the top down and engage in slots...

Page 12: ...as described in the installation section When the installation is complete do not seal surround to fireplace This will allow enough combustion air to enter the fireplace cavity and the Insert Removal...

Page 13: ...ion after a good coal base exists and wood has charred Normal Operation 1 Set air control to desired setting If smoke pours down across the glass waterfall effect this indicates you have shut the cont...

Page 14: ...ood will be producing 9375 BTU s per hour 7500 BTU x 10 lbs 8 hrs 9375 BTU s per hr If you put 20 lbs of wood in your stove for an eight hour burn you will get 18 750 BTU s per hr 7500 BTU x 20 lbs 8...

Page 15: ...ning requires small fuel loads two or three logs at a time or 1 4 to 1 2 of a fuel load and leaving the air inlet relatively wide open especially during the first 10 to 30 minutes after each loading w...

Page 16: ...it must be replaced before using the stove Re placement glass can be obtained from your Dealer The size required is 8 13 16 x 15 1 4 x 5 mm Ceramic glass must be used Do not substitute with any other...

Page 17: ...Handle Assembly WODC 4147C 13 Flame Shield WINS 4513 14 Replacement Baffle Kit SSER DBAKIT 15 Brick Rail Set SSER RAILSET 16 Firebrick Set BRIC SSERA 17 Boost Manifold 4105 18 O A Cover 4557 19 Air S...

Page 18: ...a heat storage and the thermalinsulationkeepsthecombustionzonehot Active flamingtakesplaceduringthefirstpartoftheburn During this stage heat is stored in the mass of the unit and is later released sl...

Page 19: ...Door Gasket leakage Replace gasket Check latch Low Heat Output 1 Wood is wet Use dry wood 2 Fire too small Build a larger fire 3 Area too large 4 Poor insulation or open concrete Won t Burn Overnight...

Page 20: ...lation This package contains 18 full size firebricks as well as 1 cut size brick With the heater in the upright position install firebricks as follows Place firebricks on the bottom of the heater firs...

Page 21: ...21 SPNE 190913 24 NOTES...

Page 22: ...22 SPNE 190913 24 NOTES...

Page 23: ...V9L 6V8 INSTALL AND USE ONLY IN ACCORDANCE WITH PACIFIC ENERGY S INSTALLATION AND OPERATING INSTRUCTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT CODES RESTRICTIONS AND INSTALLATION INSPECTION...

Page 24: ...PACIFIC ENERGY FIREPLACE PRODUCTS LTD www pacificenergy net Phone 1 250 748 1184 2975 Allenby Rd Duncan B C V9L 6V8 Printed in Canada...

Reviews: