background image

 

Page 1 of 8

 

TA v.12.2015

 

 

 

 

 

 

 

 

 

T

T

T

A

A

A

 

 

 

   

Domestic hot water storage tank 

 
 
 

USER AND MAINTENANCE  

MANUAL 

 

 

 

 

Cooke Industries - Phone: +64 9 579 2185  Fax: +64 9 579 2181  Email: [email protected]  Web: www.cookeindustries.co.nz

Summary of Contents for TA-S

Page 1: ... of 8 TA v 12 2015 T T TA A A Domestic hot water storage tank USER AND MAINTENANCE MANUAL Cooke Industries Phone 64 9 579 2185 Fax 64 9 579 2181 Email sales cookeindustries co nz Web www cookeindustries co nz ...

Page 2: ...orizontal version Enamelled steel cylinders TA S TA C Capacity Dimensions 5 D d H L H1 Litre mm mm mm mm mm 200 550 450 1510 1410 720 300 650 550 1550 1460 820 500 750 650 1840 1760 920 800 900 800 1910 1840 1060 1000 900 800 2160 2090 1060 1500 1050 950 2470 2360 1220 2000 1200 1100 2530 2430 1360 2500 1300 1200 2600 2500 1510 3000 1350 1250 2800 2700 1550 4000 1500 1400 2880 2800 1700 5000 1700 ...

Page 3: ...moisture absorption and the thermal stability is maintained at both high and low temperatures so that excursions from 5 C to 95 C are well supported by this enamel even with frequent cycles of maximum stress High impact resistance and very low friction coefficient allow to prevent dangerous phenomena of adhesions which are due for the most cases to calcareous deposits Low dielectric constant which...

Page 4: ...of 40 42 kg m3 average conductivity of 0 019 W mK at 45 C CFC and HCFC free Thickness Density Thermal conductivity coefficient at 45 C 55mm 40 42 kg m3 0 019 W mK PLF POLYESTHER FIBER Polyesther fiber Insulation made of soft polyesther fiber 50mm foam density of 20 kg m3 average conductivity of 0 037 W mK at 45 C CFC and HCFC free According to DPR 412 93 implementation of Italian Law 10 91 Thickne...

Page 5: ...ith water check that there is enough space around the tank in order to perform future maintenance verify that the room where the tank is located has openings of a size to allow the free passage of the cylinder in case it s necessary to bring it out in order to avoid any demolition 2 3 START The connection diagram shown in this document is purely indicative and not binding it s up to the designer o...

Page 6: ...ere s no water loss ELECTRONIC ANODE This device is not subject to wear It must be connected to the main power from which it absorbs only 3 W The titanium anode immersed in the tank is electrically feed by the device but is not consumed Be sure the power is correctly and constantly connected Short power interruptions are not dangerous and don t cause any damage Long power interruptions days or wee...

Page 7: ...reated as household waste the metallic components should be sold to operators authorized to the collection of materials for recycling the non metallic components should be transferred to operators authorized to their disposal Cooke Industries Phone 64 9 579 2185 Fax 64 9 579 2181 Email sales cookeindustries co nz Web www cookeindustries co nz ...

Page 8: ...r l Via Marconi 240 242 44122 FERRARA Tel 39 0532 774066 Fax 39 0532 773835 e mail info pacetti it web www pacetti it Cooke Industries Phone 64 9 579 2185 Fax 64 9 579 2181 Email sales cookeindustries co nz Web www cookeindustries co nz ...

Reviews: