12Volt 50Amp Low Voltage Disconnect 
(LVD) battery over-discharge protector 

 
 

Model: OC-LVD50

 

 

Important safety information, installation   

instructions and user’s manual. 

 

- - - - - - - - - - - - - - - - - - - WARNINGS - - - - - - - - - - - - - - - - - - - - - 

 

 

  Read instructions prior to use. These instructions form part of the warranty conditions. 

  Installation by competent and qualified persons only. 

  Do not attempt to use this device if it has become wet or if the cables have been damaged. 

  Do not disassemble. Take it to a qualified person if a repair is required. (No serviceable 

parts inside) 

 

Suitable for 12Volt DC systems only.

 

 

Install a fuse (maximum 50Amps) as close as possible to the battery Positive.

 

 

The main power cables must be 6.0mm

2

 (10AWG) minimum and limited in length.

 

 

The black earth/ground and blue remote wires must be 0.82mm

2

 (18AWG) minimum.

 

 