44
14.3 outputs
In this menu, the signal type and the minimum speed
can be adjusted for each individual relay of the con-
troller and the external modules.
Î
In order to make adjustments for a relay, select
the corresponding menu item by pressing button
➄
.
For each relay, the signal type and the minimum pump
speed can be adjusted.
The signal type determines the way speed control of
a connected pump is effected. The following modes
are available:
Adapter = speed control signal via a S-Bus / PWM
interface adapter
0-10 V
= speed control via a 0-10 V signal
PWM =
speed control via a PWM signal
Standard = burst control
Note:
Speed-controlled high-effi ciency pumps re-
quire two separate connections (pump con-
nection cable for power supply, signal cable
for transmitting the PWM / 0-10 V signal)
Example of the electrical connection of a high-effi ciency pump
Temp. Sensor
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
S6
S7
S8
CS1
0
V40
/S9
S-Bus
N
R4
R5
L'
VFD
PWM/0-10V
R5
RPD
IP20
2 2
2
2
2
3
3
S1
Col
St
S2
S3
R1
R2
S4
S6
VFD