Operation and Programming the Regusol Controller

Backwards key used for scrolling 
backward through the menu or to 
decrease the adjustment value

Backwards 

Forwards 

Forward key used for scrolling 
forward through the menu or 
to decrease the adjustment 

Set 

Press Set key for programming mode

2  3  1 

Operating Mode and Display

Forward or backward buttons will 
indicate following information:
COL: Collector sensor temperature
TST: Tank Temperature
hP: Operating hours counter

Programming Mod

e

To begin programming mode press forward key to 
hP display.

Press and hold forward key 1 in “hP” mode for 
2 seconds.

Menu mode displays next indicator (DT 0) and may 
now be scrolled through rest of programmable settings 
using keys 1 or 2 (forward or backward through the 
entire menu).

Values in display settings may be changed by pressing 
the Set key 3. “Set” icon will blink while in programming 
mode. Raise or lower values with keys 1 or 2. Press 
set button once more to complete change. “Set” icon 
will stop blinking.

Program Changes

“DT 0” differential turn on set point

The first program display will be “DT 0” differential turn 
on set point. DT 0 is set at 12 ºF. This indicates what 
turn on temperature the collectors must be above the 
tank to begin solar circulation. No change is necessary. 

“DT F” differential turn off set point

The second indicator will be “DT F” differential turn off 
set point. DT F is set at 5 ºF. This indicates what turn 
off temperature the collectors must be above the tank 
for solar circulation to end. No change is necessary. 

Program Changes

Mode of Operation      ON / OFF / AUTO 

“HND 1” 

 

Scroll through menu to “HND 1” display. This is 
near the end of the program display menu. This is 
for the setting switch  ON, OFF, or AUTO that 
allows the controller the function of operation. 
It is a service operation switch.

ON position energizes the pump to circulate at all 
times. 
OFF position keeps the pump from circulating.
AUTO allows the controller to operate the pump 
based on the differential temperatures (normal 
operation).

Default setting is AUTO. To change press Set key 
3. Press key 1 or 2 to change into ON, OFF or 
AUTO mode. Press set key 3 again to complete 
change and before moving into the next menu.

Always leave the controller in AUTO for normal 
solar collection cycling.

“S MX” storage maximum set point

“S MX” is set at 140 ºF. This setting can be turned 
up only if there is a anti-scald valve installed on the 
DHW system.

To change press Set key 3. Press key 1 to increase 
or 2 to decrease the storage maximum tempera-
ture. Press set key again to set change.