Assembly and installation 

 

Installation,  commissioning  and  maintenance  must  only  be 
performed  by  competent  personnel.  During  installation,  the 
respective VDE regulations are to be observed. (VDE 0100) All 
work  on  the  transformer  must  only  be  performed  in  a 

de-

energised state

 
In  order  to  prevent  heating  up  of  the  transformer  above  85°C, 
the  transformer  is  to  be  installed  in  such  a  way  its  ambient 
temperature does not exceed 40°C. It is not suited to operation 
in  or  under  water  and  in  rooms  with  ambient  temperatures 
above  40°C  or  in  rooms  with  permanent  humidity.  It  must  be 
ensured that installed protective and safety elements are acces-
sible  at  all  times.  In  order  to  ensure  sufficient  air  circulation, 
apart from the mounting surface a distance to adjacent surfaces 
of at least 10cm should be adhered to. 
Mounting  must  only  occur  as  stationary  transformer  with  fixed 
wiring.  The  transformer must  be  firmly  attached  immediately  in 
its  place  of  operation.  The  transformers  are  to  be  charged  in 
accordance with their rated output if possible.  
 
The  overall  performance  of  the  connected  consumers  must 
never  exceed  the  rated  output  of  the  transformer.  In  case  of 
branching  as  well  as  reduction  of  the  cable  cross  section,  the 
line and short-circuit protection according to VDE100 part 559 is 
to  be  ensured  during  installation.  In  general,  the  following  ap-
plies: The primary as well as secondary lines are to be protected 
against overload and short circuit.  
 

 

Important information about installation: 

The parallel circuit of the secondary side of several transformers 
is  principally  prohibited,  as  reverse  voltages  form  on  the  230V 
side. 
For an increase of the output power use a correspondingly more 
powerful transformer or additional separate transformers.  

When using several transformers, the 24-volt-circuits are to 
be separated from each other!

 

 
The  transformers  must  only  be  operated  with  laid  out  cables 
which are not bundled or rolled up. 
 
A  connecting  cable  firmly  attached  to  the  transformer  by  the 
manufacturer cannot be replaced in case of damage. The trans-
former can then no longer be operated and must be replaced. 
 
The  transformers  are  to  be  charged  in  accordance  with  their 
rated  output  if  possible.  The  power  rating  refers  to  the  perfor-
mance on secondary side during permanent operation, the rated 
input voltage, rated frequency 50/60 Hz, cos.φ 1 and an ambient 
temperature of 40°C with an installation altitude of max. 1000m 
above sea level. It is calculated from secondary rated voltage in 
volt  and  secondary  rated  current  in  ampere  to  VA  or  kVA  re-
spectively. 
 

 

Never  connect  the  secondary  side  of  several  transformers  in 
parallel, as reverse voltages form on the 230V side. 
 
 

Commissioning 

All transformers are produced in accordance with the applicable 
VDE  regulations  and  undergo  100%  electrical  routine  tests 
during  production.  The  transformers  are  built  and  designed  as 
safety transformers according to EN6155a-2-6 and are suited to 
operating systems with extra-low voltage. The low voltage trans-
formers  are  equipped  with  a  temperature  switch  which  cannot 
be reset independently.  Transformers with a capacity of 250VA 
are protected from short-circuits and overloads with an addition-
al  safety  fuse.  If  the  temperature  switch  is  actuated  due  to  an 
overload of the transformer, proceed as follows: 
 

 

Disconnect the transformer from the electrical network 

 

Eliminate the cause of the error 

 

Let the transformer cool down 

 

Transformer is ready again 

 

If  a  device  fuse  fails,  it  is  to  be  replaced  with  the  same  rated 
value with the same trip characteristic according to DIN 41662, 
lEC 127-2/111. Only fuses from the following table may be used 
as replacement fuse. 
 

Transformer capacity

  

 

Fine-wire fuse slow 

250VA 

 

 

 

T 2.00A / 250V 

 

 

Before  inserting  a  fuse  the  transformer  is  to  be  disconnected 
from the electrical network and the system is to be checked for 
any damage. 
 
 

Accessories 

See operating manual. 
 
 

Maintenance and servicing 

The  product  is  maintenance-free.  A  repair  must  only  be  per-
formed by a qualified electrician. Clean the product with a soft, 
clean,  dry  and  lint-free  cloth.  Do  not  use  any  cleaning  agents 
containing solvents or abrasive substances. The plastic housing 
and the labelling could be damaged by it.  
 
 

Declaration of conformity 

Oventrop  GmbH  &  Co.  KG  hereby  declares  that  the  appliance 
complies with the following directive. 
 

 

Low-voltage directive (LVD) 2014/35/EU  

 
The complete text of the EU declaration of conformity is availa-
ble on the Oventrop Internet page. 
 
 