“Aktor T ST”

Electrothermal actuator (0-10 V)

Das Qualitätsmanagementsystem von
Oventrop ist gemäß DIN-EN-ISO 9001
zertifiziert.

Tender specification:

Oventrop electrothermal actuator for steady control. Proportional
actuator (0-10 V) with connection thread M 30 x 1,5, closed with
current  “off”,  with  “First-Open”  function,  stroke  index  and
automatic  recognition  of  neutral  point  and  valve  travel.  The
actuator can be installed in any position. Easy plug-in connection
with valve adapter.

Model:

Item no.:

“Aktor T ST”
24 V, proportional actuator (0-10 V)

1012953

closed with current “off”

Performance data:

Operating current:

24 V AC, –10% up to +20%, 50/60 Hz

Start up load:

< 320 mA for a max. of 2 min.

Continuous current:

about 42 mA

Control voltage:

0-10 V DC

Input impedance:

100 k

W

Travel:

5.0 mm

Piston stroke:

automatic recognition

Operating power:

> 90 N

Medium floating time:

30 s/mm

Protection:

IP 54 in any position

Protective system:

III according to EN 60730

Fluid temperature:

0 °C up to 100 °C 

Ambient temperature:

0 °C up to 60 °C

Storage temperature:

-25 °C up to +60 °C

Connecting cable:

3 x 0.22 mm², length 1 m,
plug-in connection

Installation and fitting:

Electrical connection must be carried out in accordance with the
requirements of the local Electricity Board.
The connecting cable must not come into contact with the hot
pipe as excessive heat will accelerate the ageing of the cable
insulation.
When choosing the switching contacts and the network fuses, the
start up of the heating element has to be taken into consideration.
The  following  cable  lengths  are  recommended  for  a  24  V
installation:

When installing several actuators, the indicated length of cable
must be divided by the number of mounted actuators.
A safety transformer according to EN 61558-2-6 must always be
used. Dimensioning of the transformer is determined by the start
up power of the actuators. 
Rule-of-thumb:  P

Transformer

= 6 W x n

                          n = Number of actuators

Cable cross-

section [mm

2

]

24V

max. length [m]

2 x 0.22
2 x 0.80
2 x 1.50

20
45

136

“Aktor T ST”

Technical information

Dimensions

Wiring diagram

Actuator

Adapter

M 30 x 1.5

61.5

44.3

7

5

1

.1

5

3

Stroke index

b

la

c

k

b

lu

e

re

d

0-10V DC
control signal

L1

L2

24V AC