SCA-20

 

Instruction manual   

   

     

 

   

No.G1-325-14-017   

 

Please  read  the  instructions  before  installing  the  product,  as  this  instruction  manual 

explains how to use the Surge Counter effectively and safely.

 

 

1. Connection 

a) Installation of the base 

 

  1) Unfix the both side part of main body and 

     

remove the main body and terminal cover 

   

    from the base. 

 

 
 
 
 
 
 
 

b) Installation of CT 

 

  1) Earth wire for counting lightning current should be formed straight as much as possible and pass it 

through the CT. (It is not necessary to pay attention to the polarity) 

2) CT is fixed by a tying band. Use the accessary for fixing the tying band when it is fixed to the board. 

(The tying band and the accessary are not attached.)   

 

  3) If the width of cramp terminal of earth wire is less than 19mm, it can be passed through the CT. 

 

 
 
 
 
 
 

c) Connection wires 

 

 

      ・

Connect wires when power supply stops. 

      ・

Use  power  line  of  0.5  to  1.25mm

2

.    Insulation  cap  should  be  covered  on  the  connection  part  of 

terminal block or use cramp terminal with insulation tube.   

      ・

Separate lead wires of CT and signal contact from other lead wires such as power line.   
Do not twist lead wires of them to other wires, to avoid the induction by switching surge and noise. 

      ・

Twist the lead wires from CT(200mm) once per 1cm, to protect against noise. 

 

      ・

Do not extend the lead wires of CT

200mm

  to protect against noise. 

                (A malfunction might be occurred.) 

 

Connect wires of ”power source”, “CT”, “signal contact” to the base. Connect “short bar” to the base to 

change the operating current   

The size of terminal screws is M3.5 and recommendation 

      tightening torque is 0.8

1.3N

m. 

Operating current should be adjusted by short bar. 

 

10A

Short bar is not used. 

 

  50A

Short bar is connected on 

-

-

.

Initial state

 

 

  100A

Short bar is connected on 

-

-

.

 

 

Signal contact specification (a type) 

 

  The signal contact becomes “close”(500ms) when operating. 

 

  (Signal contact capacity : DC30V

 

1A,    AC125V

 

0.5A) 

After connecting wires, insert the terminal cover and the main body 

   

to the base and fix the main body by fixing parts of the base. 

 

 

 

 

 

 

2) Fix the base to DIN rail or by M4 screws. 

Note 

 

.

.

 

M4 screws 

DIN rail 

34 

14 

Fix to DIN-rail     

Fix by M4 screws 

 

押し込む 

押し込む 

 

 

Accessary for fixing the tying band (No attached) 

Less than φ19mm 

6 5 4 3

7 8 1

 

 

10A 

 

50A 

(出荷時) 

 

100A 

ショートバー 

 

接点 

Base 

CT 

      Earth wire 

Earth 

SPD 

SPD 

Load 

equipmen

Main body 

Terminal cover 

Base 

Earth wire 

Tying band 

Tying band 

Load 

equipment 

Short bar connection 

                    50A     

   

      (Initial state) 

Power input (AC100V, 

200V common use)   

 

Signal 

contact 

Push 

into 

Push 

into 

10A 

100A 