background image

 

 
Installation and operating instructions: 

 

Radio-control combined sensor 
Type: DALI LS/PD ADVANCED

 

 
 

 

 

 

OSRAM GmbH 

Hellabrunner Str. 1 

D-81536 Munich 

Tel.: +49 (0) 89 6213 – 0

 

Fax: +49 (0) 89 6213 – 2020

 

 

Customer Service Center (KSC) Germany 

Albert-Schweitzer-Str. 64 

D-81735 Munich 

Tel.: +49 (0) 1803 677 – 200 
Fax: +49 (0) 1803 677 – 202

 

          

www.osram.com 

Summary of Contents for DALI LS/PD ADVANCED

Page 1: ...bined sensor Type DALI LS PD ADVANCED OSRAM GmbH Hellabrunner Str 1 D 81536 Munich Tel 49 0 89 6213 0 Fax 49 0 89 6213 2020 Customer Service Center KSC Germany Albert Schweitzer Str 64 D 81735 Munich...

Page 2: ...Page 2 Installation instructions Combined Sensor DALI LS PD ADVANCED...

Page 3: ...Activating the sensor inserting the batteries Page 5 3 Programming in the DALI ADVANCED central unit Page 6 4 Installation Page 7 5 Detection area and shield Page 8 6 Adjustment of the sensor Page 9...

Page 4: ...lled accordingly When movement is detected the combined sensor switches the luminaires of the relevant group on and automatically starts controlling the lighting level Lighting control remains active...

Page 5: ...the new batteries Make sure they are the right way round Fig D 3 Attach the combined sensor to the base plate again by turning the unit about 45 anticlockwise until it clicks in place 4 For the first...

Page 6: ...oing so The sensor will now transmit special programming telegrams for approx 30 seconds to which the manual programming unit will react presence sensor found On the MPU enter the number of the lumina...

Page 7: ...the detection area can be restricted by means of the shield supplied see 4 Detection area and shield Do not install the combined sensor in the immediate vicinity of any heat sources such as luminaire...

Page 8: ...ction density Fig F and the sensitivity of the sensor Fig E Fig F Shield You can use the shield supplied to mask off areas that you do not wish the sensor to cover The shield is simply placed over the...

Page 9: ...button on a wall mounted or hand hald transmitter for operating the lighting controls Train the relevant channel button using the manual programming unit and then assign this button to the group to b...

Page 10: ...he measured brightness is below the setpoint e g if the weather becomes overcast If the delay time has expired because there has been no movement the lighting system will not be switched on again If t...

Page 11: ...plaster plasterboard approx 90 Brick MDF approx 70 Reinforced concrete approx 30 Metal metal grating aluminium cladding approx 10 Fig L Notes on radio operation This radio system may only be connected...

Page 12: ...on Detection angle 360 Nominal range at desk level approx 5m at floor level approx 8m Installation height for nominal range 2 5m Delay time approx 2 min to 1 h Brightness approx 3 2000 lx Temperature...