Osram DALI CON 1 – 10V SO Operating Instructions Download Page 1

 

Page 4/4 

 Operating instructions for DALI CON 1 – 10V SO 

 

Operating instructions for DALI CON 1 – 10V SO 

Page 1/4 

Wiring diagram: DALI CON 1 – 10V SO in DALI mode

  

 

(operation as converter)

 

1

2

3

4

5

6

7

10

9

8

N

L

T

DA

DA

+

-

1...10V
0...10V

DA

DA

L

N

PE

F1

10A
max

1...10V/0...10V Geräte:
EVGs, Dimmer,
elektr. Trafos usw.
Kontaktbelastbarkeit
beachten !

weitere DALI-Geräte

1...10V/0...10V

PE

N

-

+

DALI

Converter 1 - 10V
DALI CON 1 - 10V SO

 

 

Wiring diagram: DALI CON 1 – 10V SO in 1-button mode 

 (Converter as light control unit)

 

1

2

3

4

5

6

7

10

9

8

N

L

T

DA

DA

+

-

1...10V
0...10V

S1

L

N

PE

F1

10A
max

PE

N

-

+

1...10V/0...10V Geräte:
EVGs, Dimmer, 
elektr. Trafos usw.
Kontaktbelastbarkeit
beachten !

1...10V/0...10V

Converter 1 - 10V
DALI CON 1 - 10V SO

 

Subject to change without notice. Errors and omission excepted 02.03.2011 V1.2. 

Operating instructions DALI CON 1 – 10V SO  Converter from DALI to 1-10V

 

Applications and functions 

DALI converter CON 1 – 10V SO is a multifunctional unit. On the one hand it is a converter (see DALI 
mode) which is accessed digitally via the DALI interface in the same way as a DALI ECG, and on the 
other hand it is a lighting controller in its own right (see 1-button mode). With its control output 
(combined interface 1-10V/0-10V) and load contact, ECG and electronic transformers can be dimmed 
and switched via 1-10V and dimmers via 0-10V.

 

The characteristic for the control voltage at the output can be set to logarithmic 1-10V (for ECG and electronic 
transformers) or to linear 0-10V (for power dimmers) depending on the application. CON 1 – 10V SO is 
enclosed in an insulated casing in snap-on design for standard distributor installation. A unit with the identical 
function in a metal casing for installation in luminaires is also available in (DALI CON 1 – 10V LI). 

 

It is therefore possible to connect DALI with existing 1-10V/0-10V systems, combine the two systems or even 
set up separate lighting control systems. 

 

1-10V / 

linear

 characteristic  

 

 

0-10V/ 

logarithmic

 characteristic 

 

 

DALI mode (operation as converter) 

 

The converter communicates via the DALI interface with the controller (e.g. OSRAM Room Controller DALI RC 
BASIC SO). It receives DALI commands from there and also the interface supply voltage. DALI signals are 
converted to 1-10V/0-10V signals, including on/off switching via the load contact. The DALI lines (DA/DA) are 
connected to the controller for this purpose. The converter is accessed and addressed by the controller in the 
same way as a DALI ECG. All the 1-10V/0-10V units connected to the converter are considered as a uniform 
group under the address assigned to the converter. Detection of lamp faults and "physical selection" 
(deactivation and reactivation of the lamps during system startup) are 

not

 supported in the 1-10V/0-10V 

system. 
!In DALI mode, the additional switch input (T) may 

not

 be connected!

 

 

Behaviour on return of mains voltage in DALI mode (ex factory setting): 

Without the controller the load contact is closed and output voltage goes to 10 V (100%). If a controller is 
connected, the behaviour is determined by the controller (see controller description). 

1-button mode (operation as controller) 

In this mode the converter operates as an independent lighting controller with a 1-button switching/dimming 
function independently of DALI. It is operated by a switch (make contact/230Vac) which switches from input T 
to phase L. To access this mode a 

long press

 is needed (enabling the 1-button mode). The converter remains 

in this mode until it is reset to DALI mode on receipt of a DALI command via the DALI interface. 
!In 1-button mode, the DALI interface may 

not

 be connected! 

Mode I:

 

Short press: Switch On/Off, long press: Switch On-brighter/brighter/darker. 
The switch on light level is equal to the last level before switch off (automatic memory function). 

Mode II:

 

Short press: Switch On/Off, long press: Switch On-brighter/brighter/darker. 
The switch on light level is stored by a double click (= 2 x short press) in switched on state. The storage is 
signalised by flashing of the lighting. 

Change to mode I:

 Switch off the light by a short press and make a double click to the push button 

afterwards. The converter switches on with 100% light and is now in mode I. 

Change to mode II:

 Make a double click when the light is switched on. The light flashes and the current light 

level is stored as switch on level. The converter changes to mode II respectively stays in mode II.

 

Behaviour on return of mains voltage in 1-button mode: 

Switching state and dimming level are restored automatically

 

Other DALI units 

1-10V/0-10V units 
ECGs, dimmers, 
electr. Trans- 
formers, etc. 
Check contact rating! 

1-10V/0-10V units 
ECGs, dimmers, 
electr. Trans- 
formers, etc. 
Check contact rating! 