Installation
4.3
Ethernet connection
The pin-assignment of the Ethernet port corresponds to RJ45 standards.
You can use every common Ethernet component, like cable, splitters, and
switches. Connect the SYMPL dali Node at the designated Ethernet
interface with a patch cable (RJ45, CAT5).
4.4
DALI connection
The e:cue SYMPL dali Node offers a 2-pin assigned screw terminal plug for
the DALI output. Use a screw driver to open and close the terminal for
attaching the two DALI bus wires. Connect the wires according to the pin
assignment on the label.
The Node provides two terminals for each pin if the wires exceed the gauge
of the terminal plugs. In this case, please divide the wire’s end into two and
attach both cable heads in juxtaposition with each other and according to
the pin assignment to the terminal plugs.
4.5
Power supply
Connect a certified
NEC
Class 2 24 V DC power supply unit to the
SYMPL dali Node. Present power supply equates to the status “On” or
running of the SYMPL Node.
To connect the SYMPL dali Node to a power supply unit, the dali Node
provides a 2-pin screw terminal plug. Use an electrostatic sensitive screw
i
Never connect more than one SYMPL Node in factory state
to a network. The identical IP addresses will conflict and
disturb proper communication.
i
The Ethernet port of the SYMPL Node is not designed for
inter-building connections with power and lighting transients.
Use only intra-building networks to connect the SYMPL
Nodes and Cores.