Installation and operating manual for Alarm-control.plus page
3 (10)
With the colored illuminated button on the front of the housing you can:
a) Switch off the Alarm-control.plus. The device is switched off by pressing the button for 3
seconds. When the device is switched off, the button does not light up and the device does not
respond to leak sensors. The Alarm-control.plus device is switched on again by pressing the
button again.
b) Briefly press the button to turn the alarm on and off temporarily. During the pause, the backlight
of the button lights up blue. The duration of the alarm pause is limited in time. The factory setting
is 30 minutes, maximum 3 hours. After the pause time, the Alarm-control.plus device automatically
switches to signaling.
The pause in the alarm enables service work to be carried out on the water sensors without them
being triggered.
When switched on, the button lights up green until an alarm is triggered. The button flashes red
during the alarm.
If the button is mostly green but flashes red every 5 seconds, it means that one of the leak
sensors has recently had contact with water. This state must be confirmed by briefly pressing the
button.
General instruction
The control unit has been designed for safe and reliable operation in accordance with the
provisions of these operating instructions. Therefore, read these operating instructions carefully
before installing the device! The instructions contained therein for installation and operation must
be followed exactly. If these conditions are met, the control unit will work properly for many years.
Mounting
The housing is fixed vertically and permanently to a solid wall with adequate load-bearing
capacity. The place of installation must be dust-free and protected against water in order to ensure
that the device works properly. The ambient temperature should lie between 0° C and + 40° C and
should be as constant as possible. The relative humidity must not exceed 95% and no
condensation may occur. Direct incidence of heat or sunlight on the device must be avoided. The
control unit is not suitable for outdoor installation.
Electrical Connection
The control device must be fixed at a location where it is protected against moisture in accordance
with its class of protection. The power supply to the device must be fed via an all-pin main switch
with contact opening width of at least 3 mm and a residual current circuit breaker (RCCB) with I
FN
30 mA.
Before opening the housing, it is absolutely necessary to de-energize the device
electrically. The electrical connection as well as the work of adjustment and servicing
should be carried out only by an approved electrician! The connection diagrams enclosed
and the relevant safety provisions applicable must be observed and followed.
water sensor
with 2
immersion
electrodes
L N
Mains
1/N/PE
230V 50Hz
N
10 11
U2
C
NC
NO
U1
12 13
Up to 6 water sensors of different types:
L
AN
-s
o
c
k
e
t
L
AN
b
u
tt
o
n
4 5
4
white
b
ro
wn
g
re
e
n
ye
llo
w
sensor system
«Klima-2»
6 6
5
3 3
2
1 2
1
ALARM
Signal contact
potential-free
max
. 8А
K1
K2
Motor-
valve
230V
max
. 4А
Mini-
float switch
close
.
open
.