background image

ORION MINI-REP V2

CONVENTIONAL

REPEATER PANEL

MANUAL 210609

MADE IN PORTUGAL - EU

GLOBAL FIRE EQUIPMENT S.A.

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL  |  Tel: +351 289 896 560

Email: [email protected]  | Technical Support: [email protected]  | www.globalfire-equipment.com

INSTALLATION, OPERATION & MAINTENANCE MANUAL

GENERAL DESCRIPTION

The ORION MINI-REP V2

will provide remote control and system display status from multiple locations, to an ORION based

Conventional Fire Alarm System. Its reduced dimensions make it ideal for installation in reception areas or security booths
where it would be impractical and unattractive to install a full size control panel. ORION MINI-REP V2 can be connected to
the ORION Conventional Panel using 4 different interconnecting technologies: RS232, RS485, (Fiber Optics and TCP/IP
options are under development).

The unit is provided as standard with an RS232 interface. Power for the ORION MINI-REP V2 can be supplied from the
control panel’s auxiliary power output or from an external 24 Volt DC power supply if required.

IMPORTANT SAFETY NOTES

This equipment must

only be installed and maintained by a suitably qualified and technically competent person.

A basic knowledge and training in the installation of Fire Detection Systems is assumed.

The Fire Detection System should be designed by a suitably qualified person with reference to the Local Regulations
and Guidance from the fire Officer where applicable.

All wiring should be carried out with no power present in any part of the Fire Detection System.

COMPATIBILITY NOTE

ORION-MINI REP V2 repeater panel is only compatible with ORION panels that exhibit the following sequential LED
pattern during RESET.

ORION MINI-REP V2 / Installation, Operation & Maintenance Manual / © GFE 210609

1

Summary of Contents for MINI-REP V2

Page 1: ...rconnecting technologies RS232 RS485 Fiber Optics and TCP IP options are under development The unit is provided as standard with an RS232 interface Power for the ORION MINI REP V2 can be supplied from the control panel s auxiliary power output or from an external 24 Volt DC power supply if required IMPORTANT SAFETY NOTES This equipment must only be installed and maintained by a suitably qualified ...

Page 2: ...onnections should be performed with all elements of the Fire Detection System unpowered The Repeater should be located where access to the internal components is not restricted and where the unit is not exposed to high levels of moisture vibration and shock WARNING Observe ESD precautions when handling the PCBs All cables should be screened WARNING Cable screen s should only be connected at one po...

Page 3: ...CONNECTION DIAGRAMS ORION MINI REP V2 General hardware and connections layout ORION MINI REP V2 Installation Operation Maintenance Manual GFE 210609 3 ...

Page 4: ...ween Panel ORION MINI REP should be 100 meters ORION MINI REP V2 RS 485 interface Multi repeater connection until a maximum of 4 NOTE If more than one Repeater is connected in order for them to work properly some configurations are needed Please refer to the ADDRESSING THE PANEL section in this manual ORION MINI REP V2 Installation Operation Maintenance Manual GFE 210609 4 ...

Page 5: ...panel firmware FAULTS SUPPLY FAULT This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts BATTERY FAULT Indicates that there is low voltage level on the batteries or the battery charger circuit has failed AUX SUPPLY FAULT Indicates that the Auxiliary Supply has a fault EARTH FAULT When this indicator is ON there is leakage current flowing between the Earth conn...

Page 6: ...EP V2 to the ORION Conventional Panel When more than one Repeater is needed each repeater has to be addressed To address the ORION MINI REP V2 please follow the steps below 1 Install and connect the repeater refer to INSTALLATION section of this manual 2 Apply supply voltage to main panel 3 On the repeater introduce code 4321 Engineering Functions code 4 Push OUTPUTS AUXILIARY button on the DISABL...

Page 7: ...ndensing OPERATING TEMPERATURE 10ºC to 50ºC DIMENSIONS 256 L x 194 W x 75 H mm WEIGHT 1 4 Kg COLOUR CASE MATERIAL White or Red ABS GLOBAL FIRE EQUIPMENT S A Sítio dos Barrabés Armazém Nave Y Caixa Postal 908 Z 8150 016 São Brás de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire equipment com Technical Support techs globalfire equipment com www globalfire equipment com ORION MINI REP V...

Reviews: