69
VCCX2 Controller Technical Guide
No.
Relay Description
Details
1
Cooling Stage
Configured for each fixed stage of cooling (except heat pump compressor).
2
Heating Stage
Configured for each fixed stage of heating.
3
Aux Heat
Configured for a fixed stage of Aux Heat in a heat pump unit.
4
Emergency Heat
Configured for a fixed stage Emergency Heat in a heat pump unit.
5
Mod Heat Enable
Configure if a 0-10 VDC Modulating Heat source needs a relay to enable it.
6
Mod Cool Enable
Configure if a 0-10 VDC Modulating Cool source needs a relay to enable it.
7
Morning Warm-Up/
Cool-Down (VAV Boxes)
Configure (1) Relay for Morning Warm-Up/Cool-Down when Non-Orion VAV/Zone Controllers are
used.
8
Reheat
Configure (1) Relay for On/Off Reheat when used.
9
Preheat
Configure for Preheat operation.
10
Low Ambient
Configure for Low Ambient operation.
11
Exhaust Fan
Configure (1) Relay for enabling exhaust fan when Building Pressure Control is used.
12
Economizer Active
If configured, this relay will energize if unit is in Economizer Mode and the damper has moved 5% above its
Economizer Minimum Setpoint position or if the damper moves above a user-adjustable position setpoint.
13
Heat Wheel
Configure (1) Relay that turns heat wheel on when in occupied operation and turns heat wheel off
when in Economizer Mode.
14
Occupied Active
If configured, this relay will energize whenever the unit is in the Occupied Mode.
15
Override Active
If configured, this relay will energize anytime the space sensor push-button override is active.
16
Alarm Active
If configured, this relay will energize anytime a VCCX2 alarm is active.
17
A1 Comp Run Status
Will enable when the RSM A1 compressor activates.
18
A2 Comp Run Status
Will enable when the RSM A2 compressor activates.
19
B1 Comp Run Status
Will enable when the RSM B1 compressor activates.
20
B2 Comp Run Status
Will enable when the RSM B2 compressor activates.
21
Condenser Pump
If configured, this relay will energize when the unit requires the Evaporative Condenser to be enabled.
22
Sump Heater
If configured, this relay will energize when the unit requires the Sump Heater to be enabled.
23
Sump Pump Drain
If configured, this relay will energize when the unit requires the Sump Pump Drain to be enabled.
Table 4:
User-Configurable Relay Outputs
INPUTS AND OUTPUTS
12 Relay E-BUS Expansion Module