Instead of screwing the screws in all the way, it is advised to leave a space of about 2mm to
allow room for sliding the switch between the wall and the screws.
3.2 Wiring
ATTENTION
1. Be sure to disconnect the power cord before installing and/or wiring your
switches.
2. Calculate the maximum possible current in each power wire and common wire.
Observe all electrical codes dictating the maximum current allowable for each
wire size.
3. If the current goes above the maximum ratings, the wiring could overheat,
causing serious damage to your equipment.
4. Use separate paths to route wiring for power and devices. If power wiring and
device wiring paths must cross, make sure the wires are perpendicular at the
intersection point.
5. Do not run signal or communications wiring and power wiring through the same
wire conduit. To avoid interference, wires with different signal characteristics
should be routed separately.
6. You can use the type of signal transmitted through a wire to determine which
wires should be kept separate. The rule of thumb is that wiring sharing similar
electrical characteristics can be bundled together
7. You should separate input wiring from output wiring
8. It is advised to label the wiring to all devices in the system
WARNING
Do not disconnect modules or wires unless power has been switched off or
the area is known to be non-hazardous. The devices may only be connected
to the supply voltage shown on the type plate.