IO data
98
4 PR
OFINE
4-2
Input data
Data transferred from the driver to the host controller is called Input data.
Input data format
Contents of the Input data is as follows. The order of data is in big-endian format.
Byte
Size (byte)
Description
0, 1
2
Remote I/O (R-OUT)
2, 3
2
Operation data number selection_R
4, 5
2
Fixed I/O (OUT)
6, 7
2
Present alarm
8 to 11
4
Feedback position
12 to 15
4
Feedback speed (Hz)
16 to 19
4
Command position
20, 21
2
Torque monitor
22, 23
2
CST operating current
24 to 27
4
Information
28, 29
2
Reserved
30, 31
2
Read parameter ID_R
32, 33
2
Read/write status
34, 35
2
Write parameter ID_R
36 to 39
4
Read data
40 to 43
4
Assignable monitor 0
44 to 47
4
Assignable monitor 1
48 to 51
4
Assignable monitor 2
52 to 55
4
Assignable monitor 3
z
Order of 2 byte data
Example: When the CST operating current is 1,000 (0x03E8h)
Byte
Size (byte)
Description
Value (Hex)
22
2
CST operating current (upper)
0x03
23
CST operating current (lower)
0xE8
z
Order of 4 byte data
Example: When the feedback position is 300,000 (0x000493E0h)
Byte
Size (byte)
Description
Value (Hex)
8
4
Feedback position (most significant)
0x00
9
Feedback position (upper)
0x04
10
Feedback position (lower)
0x93
11
Feedback position (least significant)
0xE0