INSTRUCTIONS 

Series 1536 

DIFFERENTIAL PRESSURE INSTRUMENTS 
Diaphragm Sensor 

 

Your new Orange Research Differential Pressure Instrument is 
a rugged instrument featuring simplicity of design to provide 
dependable and efficient service.  Because it is an instrument 
it should be handled with care.  Read all instructions carefully 
before attempting to install the instrument. 

CAUTION

: Do not exceed maximum operating pressure 

listed on instrument label.  Use only fluids compatible 
with wetted parts. 

HOW IT WORKS 

The instrument operates on the difference between two 
pressures (delta-P).  The sensing element is a spring biased 
diaphragm which moves linearly in proportion to the difference 
between two basic pressures.  A magnet on the 

HI

 pressure 

side of the diaphragm/magnet assembly moves with the 
diaphragm and rotates a follower magnet located adjacent to 
the pressure cavity.  The gauge pointer is located at the end of 
the rotary magnet shaft and rotates with the magnet to provide 
gauge readings proportional to differential pressure variations. 
This is accomplished by coupling the forces between two 
adjacent magnets through a solid wall. 

Note

:

 This instrument will provide ±2% accuracy full scale. 

INSTALLATION 

This gauge is a 1516 with a porting manifold mounted to the 
back. The mounting holes on the back/bottom and the process 
ports mimic those found on the Barton 227C gauge. In fact the 
relative position of the mounting holes and the process ports is 
exactly the same as the Barton gauge, allowing you to remove 
the Barton gauge and install this unit in minutes without 
changing the position of the mounting screws and piping. 
 
If you have a Barton mounting bracket, you can reuse it on our 
gauge. 
 
The gauge can be mounted to a bracket using the mounting 
holes on the back of the pressure body, or panel mounted 
using the three holes on the dial case front flange. 
 
Most differential pressure gauges have two pressure ports, 
one for high pressure and one for a low pressure connection. 
Model 1536 has four ¼ inch FNPT ports. Two are high 
pressure ports and two are low pressure ports. The ports are 
marked 

HI

 for high and 

LO

 for low. 

 

HI-Left ports

 

– standard 

The standard configuration, called Hi-Left, has the two high 
pressure ports on the left and two low pressure ports on the 
right, as you read the dial

  

 
Hi-Right ports

 

– no charge option 

An optional Hi-Right configuration has the high pressure ports 
on the right and the low pressure ports on the left, as you read 
the dial

.

High Pressure on wrong side?

 

If you have received a gauge with the porting reversed for your 
setup, another porting manifold with opposite porting can be 
sent to you. You can easily retrofit the new porting manifold in 
the field. Please contact Orange Research to have this sent to 
you. 
 
To retrofit your unit with another porting manifold, remove the 
four bolts on the back of the unit holding the manifold. (Do not 
remove the four bolts on the side of the unit!) Remove the two 
O-rings and assemble the new porting manifold using the 
same four bolts and the new O-rings. Be sure to lightly grease 
the new O-rings so they slide into position properly. 
 
The Hi-

Left porting manifold on the back is scribed with an “A” 

on the top, while the Hi-Right porting manifold is scribed with a 
“B”. Please refer to the necessary porting manifold as Hi-Right, 
Hi-

Left or as “A” or “B” so we can be sure to send you the 

proper manifold. Please also identify the type of O-ring 
material used on your unit, since we will need to send two 
more new O-rings, and they will have to match what you have 
now. 
 
Only two of the four ports are required to measure differential 
pressure. The additional high and low ports can be used for 
bleed ports, to connect a pressure gauge or other instrument, 
or simply to connect additional piping. 
 
Two port plugs are supplied with each unit. Install them in any 
ports not being used in your installation. Teflon tape should be 
used on all port connections. Two or three wraps of Teflon 
tape are recommended. 
 
If you have selected the ½ inch NPT ports option, you will have 
received four ¼ inch to ½ inch adapters. Install them in as 
many ports as required with Teflon tape. 
 

For a Brass body the adapters are Brass 

For an Aluminum body the adapters are SS 

 

Filters

 

For filter applications, the high pressure port would be piped to 
the inlet of the filter and the low pressure port would be piped 
to the outlet of the filter. 
 

Cryogenic Tanks 

In the case of a cryogenic tank the high pressure port would 
be mated to the bottom of the tank while the low pressure port 
would be mated to the top of the tank, called the vapor space 
or the ullage. 
 

DP Flow 

For dp flow measurement, the high pressure port would be 
installed on the inlet of the primary flow element while the low 
pressure port would be installed on the outlet of the flow 
element. 
 
 