Identify and Remove the Failed DIMM
Identify and Remove the Failed DIMM
1.
Prepare the server for service.
a.
Power off the server, and disconnect the power cords from the power
supplies.
“Powering Down the Server” on page 53
.
b.
Extend the server to the maintenance position.
“Extend the Server to the Maintenance Position” on page 59
.
c.
Attach an antistatic wrist strap to your wrist and then to a metal area on the
chassis.
“Take Antistatic Measures” on page 61
.
d.
Remove the server top cover.
“Remove the Server Top Cover” on page 62
.
2.
Identify and note the location of the failed DDR4 DIMM by pressing the Fault
Remind button on the motherboard.
Servicing the DIMMs (CRU)
105
Summary of Contents for X7-2
Page 1: ...Oracle Server X7 2 Service Manual Part No E72445 03 October 2017 ...
Page 2: ......
Page 14: ...14 Oracle Server X7 2 Service Manual October 2017 ...
Page 86: ...86 Oracle Server X7 2 Service Manual October 2017 ...
Page 96: ...96 Oracle Server X7 2 Service Manual October 2017 ...
Page 110: ...110 Oracle Server X7 2 Service Manual October 2017 ...
Page 136: ...136 Oracle Server X7 2 Service Manual October 2017 ...
Page 150: ...150 Oracle Server X7 2 Service Manual October 2017 ...
Page 162: ...162 Oracle Server X7 2 Service Manual October 2017 ...
Page 168: ...168 Oracle Server X7 2 Service Manual October 2017 ...
Page 178: ...178 Oracle Server X7 2 Service Manual October 2017 ...
Page 184: ...184 Oracle Server X7 2 Service Manual October 2017 ...
Page 192: ...192 Oracle Server X7 2 Service Manual October 2017 ...
Page 216: ...216 Oracle Server X7 2 Service Manual October 2017 ...
Page 252: ...252 Oracle Server X7 2 Service Manual October 2017 ...
Page 282: ...282 Oracle Server X7 2 Service Manual October 2017 ...
Page 306: ...306 Oracle Server X7 2 Service Manual October 2017 ...