Remove an External Interconnect Assembly
Related Information
■
“Remove an External Interconnect Assembly” on page 307
■
“Install an External Interconnect Assembly” on page 311
Remove an External Interconnect Assembly
This procedure can be performed only by qualified service personnel. Remove AC power using
the circuit breakers on the appropriate PDU before performing this procedure.
1.
Determine which interconnect requires service.
“Identify Faulted Components” on page 36
2.
Take the necessary ESD precautions.
“Prevent ESD Damage” on page 61
3.
Power off the server and switch off the appropriate PDU circuit breakers.
“Removing Power From the Server or Domain” on page 69
.
4.
Locate the external interconnect assembly at the front of the server.
“CMIOU Chassis Front Components” on page 20
“Switch Chassis Front Components
5.
(Important) Label the external interconnect assembly slots and assemblies.
If you are removing one or more external interconnect assemblies and will return them to the
server (for example, because you are removing them to gain access to other components), you
must return them to their original locations in the server. Take care to properly label each slot
and assembly to ensure that it is properly reinstalled.
6.
From the rear of the server, remove the SPs or SPPs, and unseat the SP tray
from the impacted chassis.
“Servicing SP Trays” on page 243
7.
Unseat all CMIOUs and switch units from the impacted chassis.
“Servicing Switch Units” on page 189
Servicing External Interconnect Assemblies
307
Summary of Contents for SPARC M7
Page 1: ...SPARC M8 and SPARC M7 Servers Service Manual Part No E55215 06 September 2017 ...
Page 2: ......
Page 12: ...12 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 14: ...14 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 34: ...34 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 66: ...66 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 78: ...78 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 116: ...116 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 140: ...140 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 188: ...188 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 216: ...216 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 226: ...226 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 234: ...234 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 242: ...242 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 252: ...252 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 268: ...268 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 296: ...296 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 316: ...316 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...