Remove a Fan Module (CMIOU Chassis)
Caution -
This procedure requires that you handle components that are sensitive to electrostatic
discharge. This discharge can cause server components to fail. When you unpack the
replacement part, open the package on a grounded antistatic mat. Always use an antistatic wrist
strap for hardware replacements.
1.
Determine which fan module requires service.
“Identify Faulted Components” on page 36
.
2.
Take the necessary ESD precautions.
“Prevent ESD Damage” on page 61
3.
Remove the fan module.
You can remove a fan with the server running only if one fan module is faulty and if you have
a replacement fan module. If more than one module is faulty, and the server is running, it
will continue operating until a defined temperature is exceeded, at which point the server will
perform a graceful shutdown.
a.
Push the green button on the handle of the fan module to disengage the fan
latch (panel 1).
b.
Slide the fan module out to remove it from the server (panel 2).
Related Information
■
“Install a Fan Module (CMIOU Chassis)” on page 182
Servicing Fan Modules (CMIOU Chassis)
181
Summary of Contents for SPARC M7
Page 1: ...SPARC M8 and SPARC M7 Servers Service Manual Part No E55215 06 September 2017 ...
Page 2: ......
Page 12: ...12 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 14: ...14 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 34: ...34 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 66: ...66 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 78: ...78 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 116: ...116 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 140: ...140 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 188: ...188 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 216: ...216 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 226: ...226 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 234: ...234 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 242: ...242 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 252: ...252 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 268: ...268 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 296: ...296 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Page 316: ...316 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...