Install the Server (2-Post, 19-Inch Hardmount Rack Kit)
Install the Server (2-Post, 19-Inch Hardmount Rack
Kit)
Note -
The 19-inch, 2-post rackmount kit supports rack web thicknesses (the width of the rack
post) of 3 in. (76.20 mm), 4 in. (101.6 mm), and 5 in. (127 mm).
Caution -
You
must
install the server into a rack following these instructions for the 2-post,
19-inch hardmount kit. If you deviate from these instructions when installing the server, your
installation will not be supported.
1.
Gather the required tools.
“Tools Needed for Installation” on page 29
.
2.
Read the server cautions.
“Handling Precautions” on page 28
3.
Read the rack cautions and stabilize the rack.
“Stabilize the Rack” on page 33
4.
If you are changing the rack kit on an existing server in your data center, perform
these steps:
a.
Shut down the server, and remove the power and data cables.
b.
Remove the server from the rack, and place it on an antistatic mat.
c.
Remove the existing mounting brackets from the server and rack, if
applicable.
5.
Secure the side brackets to the sides of the server.
Installing the Server
53
Summary of Contents for Netra SPARC S7-2
Page 1: ...Netra SPARC S7 2 Server Installation Guide Part No E73206 03 January 2017 ...
Page 2: ......
Page 8: ...8 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 10: ...10 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 26: ...26 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 60: ...60 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 96: ...96 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 102: ...102 Netra SPARC S7 2 Server Installation Guide January 2017 ...