Install a PCIe Card in PCIe Slot 1 or 2
110
Oracle Server X6-2 Service Manual • June 2016
b.
Disconnect the rear bracket that is attached to the PCIe card from the rear of
the PCIe riser.
3.
Place the PCIe card on an antistatic mat.
Caution -
Whenever you remove a PCIe card, you should replace it with another PCIe card or
a PCIe filler panel. Installing PCIe filler panels in vacant PCIe slots helps reduce the level of
electromagnetic interference (EMI) emitted by the server. For instructions for installing a PCIe
filler panel, see
“Removing and Installing Server Filler Panels ” on page 187
.
Install a PCIe Card in PCIe Slot 1 or 2
Note -
PCIe slot 1 is nonfunctional in single-processor systems.
1.
Retrieve the PCIe card and riser you want to install.
2.
Insert the rear bracket that is attached to the PCIe card into the PCIe riser.