5.1 Probe Placement
CAUTION:
Model 924B and DMP probes must be installed as shown in this
section. If the installation cannot be done with the minimum or maximum
dimensions specified, do not continue with the installation.
Model 924B and DMP probes are safe for Class 1, Div 1, Group D hazardous
locations. This includes tanks containing regular, super, diesel and unleaded
gasoline; antifreeze; kerosene; mineral spirits; oxinol, methanol and
methanol blends; motor, torque and transmission oil; and alcohol. If you are
not sure if a product is included in this class, speak to your product specialist
or distributor.
The best location to install a probe is in the center of the tank (see the illustration below).
The probe must be installed (approximately) a minimum of three (3) feet (91 cm) from the tank fill-pipe. If the
distance is less than this interval, the force of the product that goes into the tank can cause the water float to
travel up the shaft of the probe. This can cause the controller to give an incorrect high-water alarm.
Adjust the drop-tube of the fill pipe so that the product flow is pointed away from the probe.
A Submersible Turbine Pump (STP) must be installed (approximately) a minimum of three (3) feet (91 cm)
from the probe. If the distance is less than this interval, the force of the product that the pump pulls from the
tank can cause incorrect indications of the water and product floats.
Probe Placement
Doc. No.: M2010-EU Rev.: 13
Page 34 of 149
Summary of Contents for M2010-EU
Page 6: ...Warranty 147 Doc No M2010 EU Rev 13 Page 6 of 149...
Page 20: ...Main Board Connections Jumpers and LEDs Doc No M2010 EU Rev 13 Page 20 of 149...
Page 21: ...Conduit Installation Doc No M2010 EU Rev 13 Page 21 of 149...
Page 22: ...Field Wiring Diagram Doc No M2010 EU Rev 13 Page 22 of 149...
Page 32: ...Doc No M2010 EU Rev 13 Page 32 of 149...
Page 38: ...924B Probe Installation DMP Probe Installation Doc No M2010 EU Rev 13 Page 38 of 149...
Page 41: ...Doc No M2010 EU Rev 13 Page 41 of 149...
Page 86: ...Typical Installation Drawings 30 0230 S Doc No M2010 EU Rev 13 Page 86 of 149...
Page 110: ...Appendix C Declaration of Conformity Doc No M2010 EU Rev 13 Page 110 of 149...
Page 111: ...Doc No M2010 EU Rev 13 Page 111 of 149...
Page 112: ...Doc No M2010 EU Rev 13 Page 112 of 149...
Page 113: ...Doc No M2010 EU Rev 13 Page 113 of 149...
Page 142: ...Doc No M2010 EU Rev 13 Page 142 of 149...
Page 146: ...Doc No M2010 EU Rev 13 Page 146 of 149...
Page 149: ......