l
The test is satisfactory if an alarm condition or other event related to the hydrocarbon part of the sensor
occurs. If the test results are unsatisfactory, replace the sensor.
Functional Test - Water Sensor of the Device
l
Put the end of the sensor fully into
TAP water
for at least two (2) minutes.
l
The test is satisfactory if an alarm condition or other event related to the water sensor of the device
occurs.
Clean the Hydrocarbon Sensor of the Device
l
Make sure the sensor is disconnected.
l
Put the contaminated portion of the sensor fully into
Denatured Alcohol
for one (1) hour.
l
Flush the sensor with water to remove all remaining contamination.
l
Let the sensor dry in the air for one (1) hour.
l
Reconnect the sensor.
NOTE:
If the sensor does not return to near its original resistance after you do a functional test
or contamination has been removed, it is recommended to replace the sensor.
Doc. No.: M2010-EU Rev.: 13
Page 67 of 149
Summary of Contents for M2010-EU
Page 6: ...Warranty 147 Doc No M2010 EU Rev 13 Page 6 of 149...
Page 20: ...Main Board Connections Jumpers and LEDs Doc No M2010 EU Rev 13 Page 20 of 149...
Page 21: ...Conduit Installation Doc No M2010 EU Rev 13 Page 21 of 149...
Page 22: ...Field Wiring Diagram Doc No M2010 EU Rev 13 Page 22 of 149...
Page 32: ...Doc No M2010 EU Rev 13 Page 32 of 149...
Page 38: ...924B Probe Installation DMP Probe Installation Doc No M2010 EU Rev 13 Page 38 of 149...
Page 41: ...Doc No M2010 EU Rev 13 Page 41 of 149...
Page 86: ...Typical Installation Drawings 30 0230 S Doc No M2010 EU Rev 13 Page 86 of 149...
Page 110: ...Appendix C Declaration of Conformity Doc No M2010 EU Rev 13 Page 110 of 149...
Page 111: ...Doc No M2010 EU Rev 13 Page 111 of 149...
Page 112: ...Doc No M2010 EU Rev 13 Page 112 of 149...
Page 113: ...Doc No M2010 EU Rev 13 Page 113 of 149...
Page 142: ...Doc No M2010 EU Rev 13 Page 142 of 149...
Page 146: ...Doc No M2010 EU Rev 13 Page 146 of 149...
Page 149: ......