CHECKING THE SYSTEM
SNAP PAC Redundancy Option User’s Guide
28
The information is sent to the SNAP PACs.
10.
Note the progress as the settings are applied, the device reset, and the process is completed.
11.
Click Done at the bottom of the dialog box.
Now you are ready to add the configured and commissioned system to a strategy. See the next
chapter,
Chapter 4: Creating a Strategy with Controller Redundancy
Checking the System
Use System Checkout in PAC Redundancy Manager to confirm that your system is configured and
connected correctly.
CAUTION: Be careful if you use this feature on a system that is currently running a process. During the
system check, the first PAC is checked and the second PAC’s strategy is cleared; then the strategy from the
first PAC is copied to the second PAC, and the second PAC is checked.
1.
Under Task & Tools > System Management, simply click System Checkout.