Wiring diagram - mains switching.
The link
between 3 and 5 must be fitted by the installer
Wiring diagram - volt free switching.
The dia-
gram above shows wiring for a potential-free load.
For low voltage switching connect 230v L & N to 5
& 4 respectively, and switch circuit to 3 & 2.
4. Specification
Motor:
220-240V AC 50Hz
Temperature rating
T55
Switch type:
changeover
Rating:
16A resistive / 8A inductive
Not suitable for direct switching of lighting
types: Fluorescent, HID, SON, LED
Use a contactor for discharge lamps
Suitable for fitting to surface or flush mounted
socket box. For fixed wiring only.
Class II control / Protection class IP20
Complies with European Norm
EN 60730-1: 2011
Automatic Electrical Controls for
Household and similar use,
and European Directives:
LVD; EMC; RoHS
www.tfc-group.co.uk
TFC Group LLP Tonbridge TN9 1TB
Time Switch
Socket-box timer for
general purpose use
User instructions
OP-SBST
24 Hour Synchronous
Min switching 15 minutes
OP-SBSW
7 Day Synchronous
Min switching 2 hours
(product version is shown on the rating label)
1. Set the timer
2. Manual override
3. Installation guide
4. Specification