9
4
Installation
Before installation, turn off the power switch of SC-U1 or
disconnect the power cable from the supply source and wire
the power cable after the installation is complete.
"
" denotes "Prohibited action", and "
" denotes "Required action" .
When installing the sensor,
make sure that the sensor
is oriented relative to the
water flow as shown in the
illustration. Otherwise,
suspended matter in the
water will adhere to the
detection surface and affect
the measurement value.
Do not install the sensor with
the sensor surface facing
down. Bubbles may
accumulate in the
measurement area, or the
measurement light may be
reflected off the bottom of
the facility or accumulated
objects, making it impossible
to measure correctly.
Water flow
Do not install the sensor
near a wall or other
surface. Measurement light
will strike the surface and
the reflected light will affect
the measurement values.
Install the sensor avoiding
the situation that the
sensor surface receive
strong light such as
sunlight directly.
Wall or
other
surface
Sensor installation