- 44 -
optek-Manual--1004-1010-02--ProfibusPA-US-2017-06-23
Specifications
7.11
Condensed status
Note!
The PROFIBUS
®
interface for C4000 and Haze Control supports PA profile
V3.01 with amendment 2, i.e. signalization of the process value Status
according to the above table. For amendment 2 however, it is possible to switch
over to signalization of the Status process value according to PA profile V3.01
(classic mode). The following changes for status signalization shall be observed.
The delivery status is classic mode.
Tab. 17
Condensed status
Index
Meaning according
to NE107
Usage in
PCS/DCS
Coding
Description
Quality
Quality substatus
Limits
Hex.
value
Meaning
0
Good (G)
Good
1
0
0
0
0
0
0
0
0x80
Good - OK
0
Good (G)
Good
1
0
0
0
0
0
x
x
0x84 ..
0x87
Good - update event
0
Good (G)
Good
1
0
0
0
1
0
0
1
0x89
Good - advisory alarm,
low limit
0
Good (G)
Good
1
0
0
0
1
0
1
0
0x8A
Good - advisory alarm,
high limit
0
Good (G)
Good
1
0
0
0
1
1
0
1
0x8D
Good - critical alarm,
low limit
0
Good (G)
Good
1
0
0
0
1
1
1
0
0x8E
Good - critical alarm,
high limit
1
Failure (F)
Failure
0
0
1
0
0
1
x
x
0x24 ..
0x27
Bad
2
Maintenance (M)
Good
1
0
1
0
0
1
1
0
x
x
0xA4 ..
0xAB
Good - maintenance
request
3
Check (C)
Failure
0
0
1
1
1
1
x
x
0x3C ..
0x3F
Bad - local override
4
Out of specification (S) Uncertain
0
1
1
1
1
0
x
x
0x78 ..
0x7B
Uncertain
Meaning
Hex. value in Mode condensed state
Hex. value in Mode classic mode
BAD
0x24 .. 0x27
0x0C .. 0x0F
Local override
0x3C .. 0x3F
0x00 .. 0x03
Uncertain
0x78 .. 0x7B
0x40 .. 0x43