- 30 -
optek-Manual--1004-1010-02--ProfibusPA-US-2017-06-23
Specifications
***** SET_UNCERTAIN_AS_BAD (slot index 70)
This parameter includes two functions.
Data type: Unsigned8 as single bits
With BIT 0 you can select whether a Status process value is mapped from
UNCERTAIN to BAD.
0 = UNCERTAIN is displayed.
1 = UNCERTAIN is automatically mapped on BAD state.
BIT 1 to BIT 6 serves for masking enhanced optek-specific diagnosis
information.
0 =
The corresponding diagnosis information is not displayed in
DIAGNOSIS_EXTENSION.
1 =
The corresponding diagnosis information is displayed in
DIAGNOSIS_EXTENSION.
The setting is maintained after a restart of the device.
Delivery state: 0x00
BIT 7 BIT 6
BIT 5
BIT 4
BIT 3
BIT 2
BIT 1
BIT 0
-
mask bit
Diag. ID
37
mask bit
Diag. ID
36
mask bit
Diag. ID
35
mask bit
Diag. ID
34
mask bit
Diag. ID
33
mask bit
Diag. ID
32
UNCERTAIN
AS BAD