5.2.7.1 Configure
Single PID Controller
See Section 5.2.7.2.
Control Action
Set the required control action:
Rev.
– Reverse acting – see Appendix 8.3, Fig. B2.
Direct – Direct acting – see Appendix 8.3, Fig. B3.
Proportional Band
Set the required proportional band, between 0.0 and 999.9% in 0.1% increments.
Integral Action Time
Set the integral action time, between 1 and 7200 seconds in 1 second
increments.
Set to OFF to disable integral action time.
Derivative Action Time
Set the derivative action time, between 0.1 and 999.9 seconds in 0.1 second
increments.
Set to OFF to disable derivative action time.
Output Type
Set the required output type:
Time
– Time proportioning (relay 1)
Analog – Analog output (analog output 1)
Pulse
– Pulse frequency (relay 1)
Output Type set to Time – continued on next page.
Output Type set to Analog – continued on next page.
Output Type set to Pulse – continued on page 81.
PID Controller
----
Control Action
----
Prop. Band
% Man
100.0
Output Type
Integral Time
Secs
100
Derivative Time
Secs
10.0
----
Controller
set to
PID
Rev.
Direct
Pulse
Analog
Time
Power Recovery
Pulses/Minute
Cycle Time
Output Range