Opop Biopel CS-503 Quick Start Manual Download Page 4

5.

 

CONNECTION AND COMMUNICATION 

Before activation and any kind of setup or change of parameters make sure that all boilers are connected into CS-503 
cascade controller by RC communication cable.  

In next step make communication configuration as follows: Installer settings (v8) or Main settings (v9) – Cascade – 
Connected. Communication is now active.  

Important! 

This process must be repeated separately on each connected boiler to the cascade controller.  

Next step is to select how many boilers has been connected into the cascade controller RS outputs. Go to Installer 
settings (v8) or main settings (v9) – Cascade – Number of boilers. Select number of connected boilers (4 is max).  

Important!

 You always have to connect boilers to the outputs from 1 to 4, not the opposite. Number of boilers also 

determinates  how  many  options  you  have  inside  the  menu  from  which  you  can  change  parameters  of  cascade 
operation. Factory settings is 1 boiler. Select the “Number of boilers” function on boiler which is connected into the 
1

st

 cascade controller output.   

 

6.

 

OPERATION MODES 

Setup of cascade operation is done by v8 or v9 control unit of Biopel boiler. So first ting to enable this feature is to 
update  your  boiler  control  unit  firmware.  Ask  your  installer  or  OPOP  representative  to  explain  you  which  is  the 
required  firmware  version  and  how  to  successfully  update  your  v8  or  v9  control  unit.  When  firmware  is  updated 
proceed to Installer settings and open Cascade control submenu. Following chapter is describing main functions inside 
this submenu. Read it carefully and then proceed to Installation examples chapter for examples of exact installations.   

CS-503  controller  has  2  types  of  operation  –  eqithermal  and  modulation.  These  modes  are  responsible  for  boiler 
operation if Cascade control is turned Active in Installer settings of your v8 or v9 boiler control unit. Cascade controller 
uses both outside and CH boiler temperature sensor for cascade operation.  

Important!

 Values of CH temperature and Weather temperature are red only by the boiler connected to the socket 

no.1 which is first from the left end of cascade controller.  

 

6.1.

 

Equithermal mode 

Cascade operation is based on outside weather sensor. You can select from which outside temperature level your 
boilers  starts  to  operate.    To  change  these  temperatures  you  have  to  do  the  following.  Installer  (v8)  or  Main 
settings (v9) – Cascade – and change temperature parameters:  

 

Temp of 3 boilers 

 

Temp of 2 boilers 

 

Temperature of 1 boiler 

 

Hysteresis 

 

4 boilers are in function if:  

 

external temperature is lower than “Temp of 3 boilers” minus “Hysteresis”.  

3 boilers are in function if:  

 

external temperature is lower than “Temp of 2 boilers” minus “Hysteresis”.  

 

external temperature is higher or the same as “Temp of 3 boilers” minus “Hysteresis”.  

2 boilers are in function if:  

 

external temperature is lower than “Temp of 1 boiler” minus “Hysteresis”.  

 

external temperature is higher or the same as “Temp of 2 boilers” minus “Hysteresis”.  

1 boiler is in function if:  

 

external temperature is lower than “Temp of 1 boiler” minus “Hysteresis”.   

 

Summary of Contents for Biopel CS-503

Page 1: ...ned off one by one to reduce heat production when not needed Cascade controller decreases fuel consumption extends cleaning intervals for not running boilers and makes whole hydraulic system more effi...

Page 2: ...GING 2 2 BASIC DESCRIPTION 2 3 TECHNICAL SPECIFICATION 2 4 SAFETY REQUAREMENTS 2 5 CONNECTION AND COMMUNICATION 3 6 OPERATION MODES 3 6 1 Equithermal mode 3 6 2 Modulation mode 4 7 INSTALATION EXAMPLE...

Page 3: ...current 250mA CS 503 diameters o Height 20mm o Length 100mm o Depth 40mm RS connection cable o Length 5m o Connector RS Max operational temp 20 to 45 C Package weight 35g 4 SAFETY REQUAREMENTS Read th...

Page 4: ...ings and open Cascade control submenu Following chapter is describing main functions inside this submenu Read it carefully and then proceed to Installation examples chapter for examples of exact insta...

Page 5: ...r settings v8 or Main settings v9 Cascade Lower limit of effectivity Next boiler will be deactivated after 20min from time when boiler before was deactivated This process is repeated until CH boiler t...

Page 6: ...y materials faulty design faulty design or removed as soon as at our expense provided that the device it is in normal condition according to the Instruction manual is not damaged mechanically no unaut...

Page 7: ...Vala sk Mezi Bank details Komer n banka a s account no 1608851 0100 Reg no 47674105 VAT no CZ 47674105 Phone Sales Dept 571 675 589 Secretariat 571 611 250 Production 571 675 405 Sourcing 571 675 114...

Reviews: