background image

 

OAS Open AutomationSystems GmbH 

 

Page 

1

 of 

6

 

 

OAS-SBS-IOMR-1026 

Digital outputs 16A: 4 digital outputs 16A: 4 DO relay outputs each with LED and push button 
operation  

The digital output module 

OAS-SBS-IOMR-1026 

is a Local Override/Indication Device (LO/ID) 
which is used to control four lighting circuits, or 
other digital actuators. By means of the integrated 
push buttons, it provides the ability of manual 
override of the DOs which are usually controlled 
via MODBus commands. 

The relay outputs provide the normally open 
contact of each relay and will be contacted via 
terminals. They are implemented using 

bistable 

relays

.  

For each DO there are two LEDs present  for 
indicating the status. The left LED signalizes 

whether the output is controlled via Modbus commands or whether it is manually overridden by the push 
button, whereas the right LED indicates the output's state (ON or OFF). 

The possibility of manually overriding the digital outputs by means of the push buttons can be disabled 
by using the settings in a register ('Setting the mask for manual override of the Dos’). This can be defined 
for each DO separately. Changing between the modes ‘Automatic’ and ‘Manual’ is done by holding down 
the push button. The time required for this can be set together for all four channels. If a button is pressed 
for a too short time, the left LED ('Automatic') flashes orange for one single time shortly after releasing 
the button. If, however, the channel is blocked for manual override due to the settings in the mask, this 
LED flashes permanently during the button is pressed. 

There is a register available that shows whether and which push button has been pressed since the last 
time this register has been read. When reading this register, all bits will be reset to zero. The current 
state of the push buttons and the outputs as well can also be read out via registers. 

Furthermore, via a register there can be configured whether the outputs shall start in automatic mode 
or manually overridden (OFF). In addition, a delay time can be defined, which must elapse between the 
switching of two outputs at least. Thus, the system perturbations resulting from the switching operations 
can be reduced. 

All digital outputs can be configured so that they will assume a defined state (‘safe state’) if the module 
has not received valid bus telegrams via the MODBus for a certain time. These predefined states are 
set separately for each output, whereas the time until activating the safe state is common for all outputs 
of a module. 

Reviews: