FT-3100 TRANSMITTER PROGRAMMING GUIDE
ONICON Incorporated 727.447.6140
Page 12
onicon.com
Enter the remote transmitter cable length. The allowable cable length is a
function of the fluid conductivity with a maximum allowable cable length of 164ft
(50m). Use of the remote mount transmitter option with conductivity levels of
less the 15µS/cm is not recommended. Use the table below to determine the
maximum cable length for your installation.
Sensor Cable Length
[S.cable = ft XXX]
To enter a new value, press enter to access the function. Use the right arrow key
to move the cursor and the up arrow key to change the length. Press enter to
accept the change and exit the function. Press escape to exit the program mode.
This function delays the activation of empty pipe, excitation error and signal error
alarms. The range of the delay interval is from 0 to 500 measurement cycles. For
meters up to 10” (250mm) in diameter this equates to 0 to 10 seconds. For 12” to
20” (300 to 500mm) meters, the interval range is from 0 to 25 seconds.
To enter a new value, press enter to access the function. Use the right arrow key
to move the cursor and the up arrow key to change the interval. Press enter to
accept the change and exit the function. Press escape to exit the program mode.
Alarm Delay Interval
[S.err.delay = m XXX]