CS-IO808 User Manual
CS-IO808
Serial IO Controller
Manual
Page 1: ...1 13 CS IO808 User Manual CS IO808 Serial IO Controller Manual...
Page 2: ...ring 10 2 4 1 Active Signal Wiring 11 2 4 2 Passive Switch Value Dry Contact Wiring 11 3 PARAMETERS AND WORKING MODE CONFIGURATION 11 3 1 Device and PC Connection Settings 11 3 2 Device Address 12 3 2...
Page 3: ...1 Device Usage Environment 23 5 2 FAQ 24 5 2 1 RS485 RS232 communication no response when device control 24 5 2 2 The relay can only be turned on but not turned off 25 5 2 3 485 interface cannot be us...
Page 4: ...and precautions in this manual Please open the package carefully and check whether the device and accessories have been damaged due to transportation when you receive the device Please contact us for...
Page 5: ...aud rate 300bps 38400bps It is 9600 by default and can be modified by software Support standard Modbus RTU protocol read and write by register address 253 device addresses can be set The 5 bit address...
Page 6: ...1 0 RS485 1 Address Dial CS IO204 2 4 0 RS485 1 Address Dial CS IO222A 2 2 2 0 20mA RS485 1 Address Dial CS IO404A 4 0 4 0 20mA RS485 1 Address Dial CS IO404D 4 4 0 RS485 1 Address Dial CS IO606 6 6...
Page 7: ...terminal 24 Normally ON The 4th DO normally ON terminal 25 Public The 4th DO public terminal 26 Normally ON The 5th DO normally ON terminal 27 Public The 5th1st DO public terminal 28 Normally OFF The...
Page 8: ...2 1 RS485 Wiring 2 2 2 RS232 Wiring 2 3 DO Wiring The relay is single pole double throw and each circuit has three terminals one group is normally ON and the other is normally OFF normally ON contact...
Page 9: ...9 13 CS IO808 User Manual 2 3 1 Low Load Wiring 2 3 2 AC 220V Load Device Wiring 2 3 3 AC 380V Load Device Wiring With Zero Line...
Page 10: ...Load Current 3A 4 Resistive load current 5A 2 3 5 DC Load Device Wiring 2 4 Digital Input Wiring The switch input interface is compatible with wet and dry nodes please pay attention to the different c...
Page 11: ...ion triode output liquid level detection smoke detection PLC output flow monitoring 2 4 2 Passive Switch Value Dry Contact Wiring It is suitable for passive contact signal such as various switches but...
Page 12: ...troduction The Offset Address of this device is 1 by default and the broadcast address is 254 to communicate but 0 cannot be used Communication address Offset Address 3 2 2 Device Communication Addres...
Page 13: ...de 3 3 1 Normal Mode The relay takes corresponding actions after ON or OFF command 3 3 2 NOLock Linkage Mode It is a board module with optocoupler input and DO In this mode the input optocoupler and t...
Page 14: ...art stop state 3 3 4 All Channel Lock Linkage Mode The module itself has a board module with optocoupler input and DO In this mode each time the optocoupler inputs a signal the corresponding relay wil...
Page 15: ...operation can also be directly transmitted to the relay located in the computer room module 3 3 6 2Device Lock Linkage Mode This mode requires two devices with the same address and mode to complete Af...
Page 16: ...Instruction This control card supports communication of various function codes please refer to the below Instruction code Meaning 1 Read coil register DO 2 Read Discrete Input DI 3 Read parameter regi...
Page 17: ...RS485 at the same time Spare 0x0001 41002 Spare user cannot write any value Offset address 0x0002 41003 Device address Offset address DIP switch address Working Mode 0x0003 41004 User can use store us...
Page 18: ...ster address is in accordance with the PLC naming rules the real address is to remove the highest bit and then subtract 1 4 3 Command List Scene RTU format send in hexadecimal Query 8 DOs status FE 01...
Page 19: ...00 00 01 AD C5 Return Information FE 02 01 00 91 9C Read the 2nd DI FE 02 00 01 00 01 FC 05 Read the 3rd DI FE 02 00 02 00 01 0C 05 Read the 4th DI FE 02 00 03 00 01 5D C5 Read the 5th DI FE 02 00 04...
Page 20: ...DOs Sending code FE 01 00 00 00 08 29 C3 Field Meaning Note FE Device address It is the broadcast address 01 01 command Query DO status command 00 00 Starting address Register address of the first DO...
Page 21: ...FE Device address 02 01 command Return command If the query is wrong return 0x82 01 Number of bytes All bytes of return status information 00 status of the query Return the state of the optocoupler Bi...
Page 22: ...mmand FE 10 00 03 00 02 04 00 04 00 0A 41 6B The 2nd DO flash OFF command FE 10 00 08 00 02 04 00 04 00 0A 00 D8 The 3rd DO flash OFF command FE 10 00 0D 00 02 04 00 04 00 0A C0 E7 The 4th DO flash OF...
Page 23: ...3 All OFF return code FE 0F 00 00 00 08 40 02 Field Meaning Note FE Device address 0F Off command Return command If the query is wrong return 0x82 00 00 Starting address 00 08 Quantity Number of DOs r...
Page 24: ...ity Do not use it in condensation or liquid immersion environments 6 The relay is a component with a certain service life When the theoretical service life is reached please replace it in time to avoi...
Page 25: ...er it can be can be controlled with different baud rates 5 2 4 Multiple devices on the 485 bus and ON OFF operation failed to send the broadcast address 254 If there are multiple devices on the 485 bu...
Page 26: ...specified in the terms and conditions of sale of the product And makes no warranties express or implied for the sale and or use of this product including the product s fitness for a particular purpose...