background image

Product Specification

- Mains voltage:

              /- 10%

- Mains frequency:

              50 - 60Hz

- Power Consumption:

              4VA 

- Emergency output voltage range:

              (See product label)

- Emergency Duration:

              (See product label)

- Battery:   

             (See product label)

- Allowed ambient temp:

              +5°C to +35°C

- Weight

              0.6kg

- Charging time:

              24 hours

- Protection class:

              1

- Degree of protection:

              IP20

- Em module complies with:

  

              IEC 61347-2-7

- Suitable for installation to EN50172 and BS7671

Installation & Operating Instructions

Universal Remote Emergency Pack

Installation

NOTE – 

To comply with regulations, installation must be carried out by 

a suitably qualified competent person and in accordance with the 
current IEE wiring regulations (BS7671) and building regulations.

Ensure the mains supply is isolated before attempting installation!

Page 1

19572 – Issue 1

Emergency Lighting 'standard' or 'manual' Test

The following minimum ongoing inspections and tests should be 
carried out:

Monthly
Switch off the mains power supply to the lighting unit. Inspect all 
emergency lights for satisfactory operation.  

Yearly
Switch off the mains power supply to the lighting unit. Leave the unit 
to run for the rated period (e.g. three hours). The lights should remain 
operable from the battery for the whole period.

Any defects should be noted and rectified by a competent person as 
soon as possible. Please be aware that further inspection / testing may 
be required, e.g. by risk assessment / local legislation.

Commissioning

Once the luminaire has been installed and basic emergency 
functionality checked, the battery should be allowed to charge for a 
minimum period of 24 hours before testing for its rated duration. If it 
is anticipated that the un-switched supply may be interrupted, it is 
imperative that the battery is left disconnected and commissioning is 
delayed until the supply is stable. If the luminaire has been stored for a 
number of months, it may be necessary to repeat the 
charge/discharge process several times to re-condition the battery. 
After successful commissioning, the battery box label should be 
marked with the date of the test and the Engineer responsible. 

The emergency pack is for use with LED Modules only. Please refer to the 
appropriate diagram on page 2 of this leaflet for details of mains supply, 
LED driver, battery and lamp connections.   

If non-locking external plug and socket connectors are used, i.e. without 
means to prevent accidental disconnection, the remote box should be 
sited so that it is protected from unauthorised disconnection.

A recessed plastic bezel can be found inside the packaging carton to 
assist installation of the indicator LED. A 14-16mm hole should be drilled 
in the required location so it is visible during normal use. 

Before use, the battery will need to be connected by plugging in the red 
and black lead from the hinged end of the battery box into the 
appropriate white socket, under the cover at the hinged end of the 
emergency driver. (See diagrams on page 2). 

Important:

 The battery plug and socket are polarised and should be 

connected together carefully and ensuring the polarity is correct.

To avoid subjecting the battery to excessive charge/ discharge cycles  
during installation stages, it is strongly recommend the battery is only 
connected when the mains supply is stable and the product is ready for 
commissioning.  

Once all the necessary connections have been made, use the plastic end 
covers and screws provided to secure cables in place and to prevent 
unauthorised access.

When the un-switched mains supply is turned on, the green indicator LED 
should be illuminated as follows:

- LED on:  Mains supply ok, battery connected and charging.

- LED off:  Mains supply is off [or below 160V], the battery is not connected 

or possible faulty unit.

Batteries and Disposal

The battery has a designed service life of 4 years and must be replaced 
in a timely manner to ensure the integrity of the emergency lighting 
system is maintained.  In any case, the battery should be replaced 
when it no longer provides the rated duration (3 hours).

The manufacturer of the emergency pack is committed to fulfil its 
obligations as a producer of batteries used in emergency lighting 
applications.  End-of-life batteries may either be returned to the 
emergency pack manufacturer at the customers cost and 
arrangements will be made to ensure their correct disposal.   
Alternatively it may be more convenient for the customer to deliver 
end-of-life batteries to site(s) of authorized treatment facilities at their 
cost and it will be ensured that they are accepted back and 
subsequently treated to the standard required by the regulations.

Reviews: