ON Control KSUA Manual Download Page 1

 

 

15/02/2011 

 

___________________________________________________________________  
ON control AB, Hjortstigen 5, SE-507 70 GÅNGHESTER, Sweden

 

Tel: +46 33 25 65 70, Mobile: +46 70 625 86 00, Fax: +46 33 25 69 20   

 

Page 

1

 

Beskrivning KSUA ver2_4_eng.doc

 

KSUA 

Control panel 

Valid from week of manufacture 45/2010 and 
software version 2.4 to 2.5 

Description 

The KSUA is a control and monitoring unit 
designed to control various types of fire/smoke 
dampers and fans in a flexible way. This unit is 
a master unit. Up to 32 slave units can be 
connected to the KSUA. Each slave can operate 
two damper groups, each with a maximum of 
two dampers and two smoke detector groups. 
These units can be grouped in any way in up to 
64 fire zones. Each damper group and detector 
group can be monitored individually. A central 
fire alarm system can be connected using the 
KSUC, which has a maximum capacity of 
16+16 fire zones. The KSUA can also be used 
to connect ventilation systems, smoke 
evacuation fans and heater batteries. These 
units are then controlled in an intelligent way 
depending on their function. The KSUA has 
additional inputs for an external fire alarm, 
forced opening, night mode, etc. The KSUA 
also has a standardised input for connecting a 
Modbus network monitoring all dampers, 
smoke detectors and other devices. 

General 

·

 

Master unit for KSUB 

·

 

32 slave units 

·

 

64 damper groups 

·

 

64 detector groups 

·

 

Separate KSUC unit for connecting a fire 
alarm 

·

 

Separate alarm inputs for isolating switches 
in smoke extraction fans (for example) 

·

 

2 fan groups 

·

 

6 distributed relay outputs 

·

 

Real time clock with battery backup 

·

 

External input for central fire alarm system 

·

 

Night mode input 

·

 

Forced opening input 

·

 

Evacuation dampers (pressure relief) can be 
configured in any way in the system 

·

 

Damper position indication 

·

 

Error logging 

·

 

Integrated troubleshooting program 

·

 

Compact plastic case 

·

 

Integrated transformer 

·

 

Programming using modern techniques 
(knob with pushbutton) 

·

 

Easy to back up the configuration 

·

 

Serial or TCP/IP Modbus 

·

 

And more 

 

Maximum configuration 

The system can handle a total of 64 damper 
groups with a maximum of 128 dampers and 
64 detector inputs. In principle, an unlimited 
number of smoke detectors can be connected. 
These smoke detector inputs and fire dampers 
can then be grouped into a maximum of 64 fire 
zones. 16+16 fire zones come from the KSUC. 
There are up to two outputs for fan control. 
Using the KSUC, a further 6 outputs are 
available. These outputs can be configured for 
ventilation fans, smoke extraction fans, various 
alarms or heater batteries. Custom delays, etc. 
can be selected for each of the options.  
 

Summary of Contents for KSUA

Page 1: ...dised input for connecting a Modbus network monitoring all dampers smoke detectors and other devices General Master unit for KSUB 32 slave units 64 damper groups 64 detector groups Separate KSUC unit...

Page 2: ...ter batteries or smoke extraction fans can be programmed with different time delays Inputs Modbus slave RS485 Available as a screw terminal or standardised RJ45 contact Bus for KSUB and KSUC slave uni...

Page 3: ...end and one of the slaves at the other Both units must then be terminated with the built in resistors i e jumper I in the KSUB and jumper PL2 or PL3 in the KSUA PL3 is used for the Modbus connection...

Page 4: ...rced insulation so no ground is necessary SBus ISbus Connect one slave at a time each with a unique address so that not too many errors occur at the same time Make sure the network is correctly connec...

Page 5: ...output is hard coded so that detector group 1 is connected to KSUB address 0 Detector group 2 is connected to KSUB address 1 etc up to detector group 12 The KSUB fan relay output is dependent on the...

Page 6: ...ion dampers have opened or after 20 seconds For the function test the running time can be set between 10 and 900 seconds Fuses There is a 100mAT fuse on the motherboard To access the fuse remove the f...

Page 7: ...etector Groups 4 Damper Status 5 Detector Status 6 Relays Inputs 17 Fan relays 14 Configuration For Damper 16 Detector Group Members Relay 1 Relay 2 33 Select Detector Groups Operation Status View 32...

Page 8: ...est from a slave KSUC1 STATUS 65e 80e 6666677777777778 5678901234567890 Not Installed 7 and 8 The active inputs in the KSUC are displayed here Inactive inputs appear as and if there is no unit Not Ins...

Page 9: ...cluded in a detector group A detector can be included in more than one group The stars on the right indicate that the detector is included in the group SETTINGS Damper Table 6 Detector groups Fan Rela...

Page 10: ...lays in the KSUA Menus 18 to 23 are used to change the settings SETTINGS ModBus I O Print Settings Change Password 21 This function is used to document the entire installation The Modbus port is used...

Page 11: ...mit of 40mA is reached This will trigger a real smoke alarm more or less affecting the entire system A manual reset is required after an automatic function test The FAN 1 output has probably been conn...

Reviews: