Parallel I/O connection
ZW User's Manual
147
6
Commun
ication
s with Exte
rnal De
vi
ces
Explorer pane
: [Bank] | [(Bank Data Name)] (double click)
Edit pane
: [I/O Settings] icon (
)
I/O Setting Screen
: [Binary output]
Decimal point digit setting
Sets the number of digits after the decimal point for data output as binary.
Example:
If the measured value is "0.123456", the output value is as follows according to the number of digits after the
decimal point.
0 digits: 0 (output range: 1048576 mm - 1048575 mm)
1 digit: 1 (output range: 104857.6 mm - 104857.5 mm)
2 digits: 12 (output range: 10485.76 mm - 10485.75 mm)
3 digits: 123 (output range: 1048.576 mm - 1048.575 mm)
4 digits: 1234 (output range: 104.8576 mm - 104.8575 mm)
5 digits: 12345 (output range: 10.48576 mm - 10.48575 mm)
6 digits: 123456 (output range: 1.048576 mm - 1.048575 mm)
If the measurement result is outside the output range, the output range upper or lower limit is output.
For example, if the number of digits after the decimal point is 6 and the measurement result is 2.00000 mm,
the binary output value is 1048575.
If there is a measurement abnormality, the output range upper limit value is output.
1
Set the operating mode to the FUN mode.
3-3 Switching operation modes p.57
2
Select the task from [Output object].
Binary output can also be assigned with key operations on the Sensor Controller.
Item
Setting item
Setting value
Description
Binary output
Decimal point
digit
0 digit/1 digit/2 digits/3 digits/4
digits/5 digits (Default value) /6
digits
Sets the number of digits after the decimal point for data
output as binary.
Note
Summary of Contents for ZW-C1*T
Page 70: ...Operating with Sensor Controller 68 ZW User s Manual MEMO ...
Page 116: ...Setting the System 114 ZW User s Manual MEMO ...
Page 134: ...Controll input signal with PC tool 132 ZW User s Manual MEMO ...
Page 209: ...8 Troubleshooting Troubleshooting 8 1 Error Messages 208 8 2 Troubleshooting 210 ...
Page 319: ...Index ZW User s Manual 317 Index 11 ...
Page 321: ......