24
Sec
tion 2
Wiring
RFID System
Operation Manual
Section 2
Installation and Wiring
Wiring
Power Supply and Ground
• The power supply and ground terminals use M3 self-rising terminals. If using crimp terminals for
wiring, use ones with the following specifications.
Recommended tightening torque: 0.5 N·m
Examples of Applicable Crimp Terminals
Examples of Applicable Crimp Terminals
Manufacturer
Model
Applicable wire
size
Shape
J.S.T. Mfg Co.
1.25-N3A
0.25 to 1.65 mm
2
(AWG22 to
AWG16)
Forked
V1.25N3A
1.25-MS3
Round
V1.25-MS3
6.4 max.
(for M3
terminals)
6.4 max.
Supply 24 VDC to the ID Controller. Make sure that the
voltage fluctuation is within the range of 20.4 to 26.4
VDC (24 VDC+10%/
15%).
Recommended DC Power Supply: Compact, DIN-rail Mounting
(Manufactured by OMRON)
Model
Output capacity
Input current
S8VS-03024
1.3 A at 24 VDC
100 to 240 VAC
Countermeasures against noise superimposed on
power lines is provided in the IC Controller. Supplying
power through a filter can be used to substantially
reduce ground noise.
Although the rated power consumption of the ID Controller is
1.3 A at 24 VDC (30 W), determine the capacity by taking the
inrush current into consideration.
Use a twisted-pair cable for the power supply line.
To improve noise immunity, ground to 100
or less and
use a dedicated ground.
Use a class-2 power supply.
+24 V
0 V
Line filter
Ground to 100
or less
using a dedicated ground
DC p
o
w
e
r sup
p
ly