Ambient Temperature
• Maintain a minimum clearance of 50 mm above and
below the V530-R160 to improve air circulation.
• Do not install the V530-R160 immediately above signifi-
cant heat sources, such as heaters, transformers, or
large-capacity resistors.
• Do not let the ambient operating temperature exceed
50
°
C (122
°
F).
• Provide a forced-air fan or air conditioning if the ambient
temperature is near 50
°
C (122
°
F) so that the ambient
temperature never exceeds 50
°
C (122
°
F).
Noise Resistance
• Do not install the V530-R160 in a cabinet containing high-voltage equipment.
• Do not install the V530-R160 within 200 mm of power
cables.
Component Installation and Handling
OMRON Components
Be sure to use the Camera, Camera Cable, and Console designed for the V530-R160.
Refer to page 36.
Cameras and Cables
Always turn OFF the power before connecting or disconnecting cameras or cables.
Cameras
The camera's case is connected to the 0 V line in the internal circuits. Heed the following precau-
tions to prevent noise interference.
• Do not ground the Camera.
• Do not remove the base attached to the Camera.
• Do not remove the core attached to the V530-VS-2D Camera Cable.
Control Box
V530-R160
Louver
V530-R160
200 mm min.
200 mm min.
Power Cable