3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-6
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
_EIP1_IPAdrCfgErr
Port1 IP Address Set-
ting Error
Indicates the IP address setting errors for
the communications port 1.
TRUE:
•
There is an illegal IP address
setting.
•
A read operation failed.
•
The IP address obtained from
the BOOTP server is incon-
sistent.
FALSE: Normal
BOOL
TRUE or
FALSE
_EIPIn1_IPAdrCfgErr
Internal Port1 IP
Address Setting Error
Indicates the IP address setting errors for
the internal port 1.
TRUE:
•
There is an illegal IP address
setting.
•
A read operation failed.
•
The IP address obtained from
the BOOTP server is incon-
sistent.
FALSE: Normal
BOOL
TRUE or
FALSE
_EIP_IPAdrDupErr
IP Address Duplica-
tion Error
NY-series Controller: Indicates that the
same IP address is assigned to more than
one node for the communications port 1.
TRUE: Duplication occurred.
FALSE: Other than the above.
BOOL
TRUE or
FALSE
_EIP1_IPAdrDupErr
Port1 IP Address
Duplication Error
Indicates that the same IP address is
assigned to more than one node for the
communications port 1.
TRUE: Duplication occurred.
FALSE: Other than the above.
BOOL
TRUE or
FALSE
_EIPIn1_IPAdrDupErr Internal Port1 IP
Address Duplication
Error
Indicates that the same IP address is
assigned to more than one node for the
internal port 1.
TRUE: Duplication occurred.
FALSE: Other than the above.
BOOL
TRUE or
FALSE
_EIP_DNSCfgErr
DNS Setting Error
Indicates that the DNS or hosts settings
are incorrect. Or, a read operation failed.
TRUE: Setting incorrect or read failed
FALSE: Normal
BOOL
TRUE or
FALSE
_EIP_BootpErr
BOOTP Server Error
NY-series Controller: Indicates that a
BOOTP server connection failure
occurred on the communications port 1.
TRUE: There was a failure to connect to
the BOOTP server (timeout).
FALSE: The BOOTP is not enabled, or
BOOTP is enabled and an IP
address was normally obtained
from the BOOTP server.
BOOL
TRUE or
FALSE
_EIP1_BootpErr
Port1 BOOTP Server
Error
Indicates that a BOOTP server connection
failure occurred on the communications
port 1.
TRUE: There was a failure to connect to
the BOOTP server (timeout).
FALSE: The BOOTP is not enabled, or
BOOTP is enabled and an IP
address was normally obtained
from the BOOTP server.
BOOL
TRUE or
FALSE
Variable name
Meaning
Function
Data type
Range of
values
Reference
Summary of Contents for Sysmac NY512-1300
Page 459: ......