Variable name
Meaning
Function
Data type
Range of
values
Reference
_EIP1_CipErr
CIP Communica-
tions1 Error
This is the error status variable for CIP
communications 1.
It represents the collective status of the
following error flags.
•
_EIP1_IdentityErr (CIP Communica-
tions1 Identity Error)
•
_EIP1_TDLinkCfgErr (CIP Communi-
cations1 Tag Data Link Setting Error)
•
_EIP1_TDLinkOpnErr (CIP Communi-
cations1 Tag Data Link Connection
Failed)
•
_EIP1_TDLinkErr (CIP Communica-
tions1 Tag Data Link Communications
Error)
•
_EIP1_TagAdrErr (CIP Communica-
tions1 Tag Name Resolution Error)
•
_EIP1_MultiSwONErr (CIP Communi-
cations1 Multiple Switches ON Error)
Note
If a Tag Name Resolution Error
occurs, it is recorded in the
event log and this variable
changes to TRUE. Refer to in-
formation on the meanings of
the error status bits at the end
of this appendix for details.
Note
You can use this system-de-
fined variable only for NX-ser-
ies CPU Units.
WORD
16#0000 to
16#00F0
_EIP2_CipErr
CIP Communica-
tions2 Error
This is the error status variable for CIP
communications 2.
It represents the collective status of the
following error flags.
•
_EIP2_IdentityErr (CIP Communica-
tions2 Identity Error)
•
_EIP2_TDLinkCfgErr (CIP Communi-
cations2 Tag Data Link Setting Error)
•
_EIP2_TDLinkOpnErr (CIP Communi-
cations2 Tag Data Link Connection
Failed)
•
_EIP2_TDLinkErr (CIP Communica-
tions2 Tag Data Link Communications
Error)
•
_EIP2_TagAdrErr (CIP Communica-
tions2 Tag Name Resolution Error)
•
_EIP2_MultiSwONErr (CIP Communi-
cations2 Multiple Switches ON Error)
Note
If a Tag Name Resolution Error
occurs, it is recorded in the
event log and this variable
changes to TRUE. Refer to in-
formation on the meanings of
the error status bits at the end
of this appendix for details.
Note
You can use this system-de-
fined variable only for the
NX701 CPU Units and NX102
CPU Units.
WORD
16#0000 to
16#00F0
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-8
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......