7-3
Ladder Programming for Tag Data
Links
7-3-1
Ladder Programming for Tag Data Links
The following conditions 1 to 3 should be fulfilled if you use tag data link data for a ladder program.
The additional conditions 4 and 5 should be also fulfilled if you input the Controller information of the
target node.
Conditions for enabling tag data links for the built-in EtherNet/IP port on a
NJ/NX-series CPU Unit
The following conditions 1 and 2 should be both fulfilled.
No.
Condition
1
The following error status bits in the
_EIP_ErrSta
(Built-in EtherNet/IP Error) variable
are FALSE.
•
Major fault: Bit 7
•
Partial fault: Bit 6
•
Minor fault: Bit 5
2
The
_EIP_EtnOnlineSta
(Online) variable
*1
is TRUE.
Condition for tag data links with connection established to the target de-
vice
The following condition 3 should be fulfilled.
No.
Condition
3
In the
_EIP_EstbTargetSta
(Normal Target Node Information) variable
*2
, the bit corre-
sponding to the target node address is TRUE.
Condition of the Controller operating mode (operating or stopped) (only
for OMRON Controllers)
The following condition 4 should be fulfilled.
No.
Condition
4
In the
_EIP_TargetPLCModeSta
(Target PLC Operating Mode) variable
*3
, the bit cor-
responding to the target node address is TRUE.
Condition of the Controller error status (fatal or non-fatal error) of the tar-
get node (only for OMRON Controllers)
The following condition 5 should be fulfilled.
No.
Condition
5
In the
_EIP_TargetPLCErr
(Target PLC Error Information) variable
*4
, the bit corre-
sponding to the target node address is FALSE.
When you want to use the Target Node Controller Error Flag, the Controller status
must be included in the tag sets for both the originator and target. Include the Control-
ler status by using the Network Configurator to select the Include Option in the Edit
Tag Set Dialog Box.
7 Tag Data Link Functions
7-80
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......