Additional Information
With a CPU Unit with unit version 1.04 or later that operates as the originator device, a
Tag
Data Link Connection Timeout
error will occur if a connection is not established with the target
device within one minute after the tag data links are started.
Even after this error occurs, reconnection processing is continued periodically until automatic
recovery is performed.
If the application environment allows you to ignore this error, such as when a target device is
started later than the originator device, you can change the event level to the observation level.
Starting and Stopping Tag Data Links for the Entire Network
You can start and stop tag data links for the entire network from the user program or from the Network
Configurator.
Precautions for Correct Use
Use the same method (i.e., either the user program or the Network Configurator) to both start
and stop tag data links.
For example, if you use the
_EIP_TDLinkStopCmd
(Tag Data Link Communications Stop
Switch) system-defined variable stop tag data links, you cannot start them from the Network
Configurator.
Using Commands in the User Program
You can start and stop tag data links on a device basis by changing the values of the following sys-
tem-defined variables from FALSE to TRUE in the user program. (Refer to
fined Variables Related to the Built-in EtherNet/IP Port
• NX701 CPU Unit and NX102 CPU Unit
You can individually start and stop tag data links for each built-in EtherNet/IP port.
• Tag data links start/stop operation switch for built-in EtherNet/IP port 1
_EIP1_TDLinkStartCmd
(CIP Communications1 Tag Data Link Communications Start Switch)
_EIP1_TDLinkStopCmd
(CIP Communications1 Tag Data Link Communications Stop Switch)
• Tag data links start/stop operation switch for built-in EtherNet/IP port 2
_EIP2_TDLinkStartCmd
(CIP Communications2 Tag Data Link Communications Start Switch)
_EIP2_TDLinkStopCmd
(CIP Communications2 Tag Data Link Communications Stop Switch)
• NX1P2 CPU Unit:
_EIP1_TDLinkStartCmd
(CIP Communications1 Tag Data Link Communications Start Switch)
_EIP1_TDLinkStopCmd
(CIP Communications1 Tag Data Link Communications Stop Switch)
• NJ-series CPU Unit:
_EIP_TDLinkStartCmd
(Tag Data Link Communications Start Switch)
_EIP_TDLinkStopCmd
(Tag Data Link Communications Stop Switch)
7 Tag Data Link Functions
7-69
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
7-2 Setting T
ag Data Links
7
7-2-12
Starting and Stopping T
ag Data Links
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......