3
You can change tag set names in this dialog box. To confirm a change, click the
Regist
Button
in the
Edit Tag Set
Dialog Box.
4
Perform steps 1 to 3 for all the devices to which tag data links are made to import variables and
to create tag sets.
7-2-5
Connection Settings
After you create the tag sets, click the
Connections
Tab at the top of the
Edit Device Parameters
Dialog Box, and set the following connection information.
• The target devices and tag sets with which connections are opened
• The connection type (multicast or unicast)
• The length of the packet intervals (RPI)
• Connection name (optional)
Make the connections settings on the originator only. The connections settings are not necessary on
the target device.
Precautions for Correct Use
Make the connections settings after you create tag sets for all of the devices involved in tag da-
ta links.
Connection Settings (Connections Tab Page)
Registering Devices in the Register Device List
1
Double-click the icon of the device for which to make originator settings in the Network Config-
uration Pane of the Network Configurator. The
Edit Device Parameters
Dialog Box is dis-
played. Or, right-click the icon to display the pop-up menu, and select
Parameter
–
Edit
.
2
Click the
Connections
Tab in the
Edit Device Parameters
Dialog Box.
All of the devices registered in the network (except the local node) are displayed.
7 Tag Data Link Functions
7-36
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
Summary of Contents for Sysmac NX1P2-10 1 Series
Page 8: ...Manual Structure 6 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 34: ...Revision History 32 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 388: ...9 Socket Service 9 34 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 430: ...12 FTP Client 12 14 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 569: ...I Index I 1 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506 I...
Page 576: ...Index I 8 NJ NX series CPU Unit Built in EtherNet IP Port User s Manual W506...
Page 577: ......