4 - 5
4 Installation and Wiring
E3X-ECT EtherCAT Sensor Communication Unit Instraction Manual
4-2 C
o
n
n
ect
ing t
o
Et
herCA
T
Net
w
o
rk
4
4-
2-2 Pr
ep
arat
ion for
Conne
cting Netw
ork
Prepare the following devices.
Precautions for Correct Use
•
The maximum cable length between connected nodes is 100 m. Note that some cables do not
guarantee 100 m. In general, if the conductors are strand wire, the transmission performance
will be lower than solid wire and the operation at 100-m distance cannot be guaranteed.
Confirm details with the cable manufacturer.
•
When selecting connectors, check that the cables to be used conform to connectors. Items to
be checked include conductor size, conductor wire type (solid wire/twisted wire, 2/4 pairs), and
outer diameter.
Reference
We recommend cables with double, aluminum tape and braded shielding, taking noise
resistance into consideration.
4-2-2
Preparation for Connecting Network
Product name
Comment
Twisted-pair cable
(Cables with connectors
below are also allowed.)
100BASE-TX (Category 5 or higher)
Double-shield (aluminum tape + braided shielding)
RJ45 connector
Category 5 or higher
Shielded
Summary of Contents for Sysmac E3X-ECT
Page 1: ...E3X ECT EtherCAT Sensor Communication Unit Operation Manual E413 E1 ...
Page 3: ......
Page 4: ...E3X ECT EtherCAT Sensor Communication Units Operation Manual Revised February 2012 ...
Page 5: ......
Page 29: ...1 EtherCAT Network 1 8 E3X ECT EtherCAT Sensor Communication Unit Instration Manual ...
Page 51: ...4 Installation and Wiring 4 12 E3X ECT EtherCAT Sensor Communication Unit Instraction Manual ...
Page 67: ...5 EtherCAT Communications 5 16 E3X ECT EtherCAT Sensor Communication Unit Instraction Manual ...
Page 137: ...A Appendix A 36 E3X ECT EtherCAT Sensor Communication Unit Instraction Manual ...
Page 139: ...Revision 2 E3X ECT EtherCAT Sensor Communication Unit Instraction Manual ...
Page 140: ......