55
Specifications
Section 2-2
2-2-3
I/O Specifications for XA and X CPU Units
Relationship between Built-in Inputs and Terminal Block Arrangement
Terminal Block Arrangement
TR Area
16 bits: TR0 to TR15
HR Area
8,192 bits (512 words): H0.00 to H511.15 (words H0 to H511)
AR Area
Read-only (Write-prohibited)
7,168 bits (448 words): A0.00 to A447.15 (words A0 to A447)
Read/Write
8,192 bits (512 words): A448.00 to A959.15 (words A448 to A959)
Timers
4,096 bits: T0 to T4095
Counters
4,096 bits: C0 to C4095
DM Area
32 Kwords: D0 to D32767
Note
Initial data can be transferred to the CPU Unit's built-in flash memory using the
data memory initial data transfer function. A setting in the PLC Setup can be
used so that the data in flash memory is transferred to RAM at startup.
DM Area words for CJ-series Special I/O Units:
D20000 to D29599 (100 words
×
96 Units)
DM Area words for CJ-series CPU Bus Units:
D30000 to D31599 (100 words
×
16 Units)
DM fixed allocation words for Modbus-RTU Easy Master
D32200 to D32249 for Serial Port 1, D32300 to D32349 for Serial Port 2
Data Register Area
16 registers (16 bits): DR0 to DR15
Index Register Area
16 registers (16 bits): IR0 to IR15
Task Flag Area
32 flags (32 bits): TK0000 to TK0031
Trace Memory
4,000 words (500 samples for the trace data maximum of 31 bits and 6 words.)
Type
X CPU Units
XA CPU Units
Y CPU Units
Model
CP1H-X40DR-A
CP1H-X40DT-D
CP1H-X40DT1-D
CP1H-XA40DR-A
CP1H-XA40DT-D
CP1H-XA40DT1-D
CP1H-Y20DT-D
L1
L2/N COM
01
03
05
07
09
11
01
03
05
07
09
11
00
02
04
06
08
10
00
02
04
06
08
10
Upper Terminal Block (Example: AC Power Supply Models)
Inputs (CIO 0)
Outputs (CIO 1)
Normal input terminals
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......