600
Error Classification and Confirmation
Section 11-1
11-1 Error Classification and Confirmation
Error Categories
Errors in CP1H CPU Units can be broadly divided into the following four cate-
gories.
Confirming Errors
There are three sources of information on errors that have occurred.
• CPU Unit indicators
• Seven-segment display
• Auxiliary Area
CPU Unit Indicators
These indicators show the operating status of the CPU Unit.
Note
Do not turn OFF the CPU Unit power supply when this indicator is lit.
Category
Comments
CPU Error
A WDT (watchdog timer) error is generated in the CPU Unit, the
CPU Unit will malfunction, and operation will stop.
CPU Standby
The CPU will go on standby because conditions for stating oper-
ation have not yet been met.
Fatal Error
Operation cannot continue. Operation will stop due to a serious
problem.
Non-fatal Error
A minor problem has occurred. Operation will continue
POWER
RUN
INH
PRPHL
BKUP
ERR/ALM
POWER
(green)
Lit
Power is ON.
Not lit
Power is OFF.
RUN (green)
Lit
The CPU Unit is executing a program in either RUN or
MONITOR mode.
Not lit
Operation is stopped in PROGRAM mode or due to a
fatal error.
ERR/ALM
(red)
Lit
A fatal error or CPU error (WDT error) has occurred.
operation will stop and all outputs will be turned OFF.
Flashing
A non-fatal error has occurred. Operation will continue.
Not lit
Operation is normal.
INH (yellow)
Lit
The Output OFF Bit (A500.15) was turned ON. All out-
puts will be turned OFF.
Not lit
Operation is normal.
BKUP
(yellow)
(See note.)
Lit
The built-in flash memory is being written to or the
Memory Cassette is being accessed.
The BKUP indicator also lights while the user program
is being restored when the power supply is turned ON.
Not lit
Other than the above.
PRPHL
(yellow)
Flashing
Communications (either sending or receiving) are in
progress through the peripheral port.
Not lit
Other than the above.
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......