379
Program Protection
Section 6-6
2.
The entire program can be transferred to another CPU Unit even if individ-
ual tasks in the program are read-protected. The task read protection will
remain in effective for the password-protected tasks.
3.
When the CX-Programmer is used to compare a user program in the com-
puter's memory with a user program in the CPU Unit, password-protected
tasks will be compared too.
Restrictions to Function
Block Use
Function block definitions can be read even if the entire program or individual
tasks in a program containing function blocks are read-protected.
Auxiliary Area Flags and Bits Related to Password Protection
6-6-2
Write Protection
Write-protection
Using the DIP Switch
The user program can be write-protected by turning ON pin 1 of the CPU
Unit’s DIP switch. When this pin is ON, it won’t be possible to change the user
program or parameter area (e.g., PLC Setup and routing tables) from the CX-
Programmer. This function can prevent the program from being overwritten
inadvertently at the work site.
It is still possible to read and display the program from the CX-Programmer
when it is write-protected.
Name
Bit
address
Description
UM Read Protection
Flag
A99.00
Indicates whether or not the PLC (the entire user
program) is read-protected.
OFF: UM read protection is not set.
ON: UM read protection is set.
Task Read Protection
Flag
A99.01
Indicates whether or not selected program tasks
are read-protected.
OFF: Task read protection is not set.
ON: Task read protection is set.
Program Write Protec-
tion for Read Protec-
tion
A99.02
Indicates whether or not the write protection
option has been selected to prevent overwriting
of password-protected tasks or programs.
OFF: Overwriting allowed
ON: Overwriting prohibited (write-protected)
Enable/Disable Bit for
Program Backup
A99.03
Indicates whether or not a backup program file
(.OBJ file) can be created when UM read protec-
tion or task read protection is set.
OFF: Creation of backup program file allowed
ON: Creation of backup program file prohibited
UM Read Protection
Release Enable Flag
A99.12
Indicates when UM read protection cannot be
released because an incorrect password was
input five times consecutively.
OFF: Protection can be released
ON: Protection cannot be released
Task Read Protection
Release Enable Flag
A99.13
Indicates when task read protection cannot be
released because an incorrect password was
input five times consecutively.
OFF: Protection can be released
ON: Protection cannot be released
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......