Internal I/O Area
Section 4-9
4-9
Internal I/O Area
The Internal I/O (Work) Area contains 512 words with addresses ranging from
W0 to W511. These words can be used in programming as work words.
There are unused words in the CIO Area (CIO 1200 to CIO 1499 and
CIO 3800 to CIO 6143) that can also be used in the program, but use any
available words in the Work Area first because the unused words in the CIO
Area may be allocated to other applications when functions are expanded.
Forcing Bit Status
Bits in the Work Area can be force-set and force-reset.
Work Area Initialization
The contents of the Work Area will be cleared in the following cases:
1.
When the operating mode is changed from PROGRAM to RUN or MONI-
TOR mode or vice-versa and the IOM Hold Bit is OFF
2.
When the power is cycled
3.
When the Work Area is cleared from the CX-Programmer.
4.
When PLC operation is stopped when a fatal error other than an
FALS(007) error occurs. (The contents of the Work Area will be retained
when FALS(007) is executed.)
4-10 Holding Area (H)
The Holding Area contains 512 words with addresses ranging from H0 to
H511 (bits H0.00 to H511.15). These words can be used in programming.
Holding Area Initialization
Data in the Holding Area is not cleared when the power is cycled or the PLC’s
operating mode is changed from PROGRAM mode to RUN or MONITOR
mode or vice-versa.
A Holding Area bit will be cleared if it is programmed between IL(002) and
ILC(003) and the execution condition for IL(002) is OFF. To keep a bit ON
even when the execution condition for IL(002) is OFF, turn ON the bit with the
SET instruction just before IL(002).
Self-maintaining Bits
When a self-maintaining bit is programmed with a Holding Area bit, the self-
maintaining bit won’t be cleared even when the power is reset.
Note
1.
If a Holding Area bit is not used for the self-maintaining bit, the bit will be
turned OFF and the self-maintaining bit will be cleared when the power is
reset.
2.
If a Holding Area bit is used but not programmed as a self-maintaining bit
as in the following diagram, the bit will be turned OFF by execution condi-
tion A when the power is reset.
3.
H512 to H1535 are used as a Function Block Holding Area. These words
can be used only for function block instances (internally allocated variable
H0.00
H0.00
A
H0.00
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......